Frequency Inverter ST600 Series High-Performance Multifunction VFD Expansion cards
-319-
PS5—COM
Digital input 5
5. Both source and sink inputs are allowed, but
the input types must be the same
PS6—COM
Digital input 6
Analog input and
output
AI1
Analog input 1
1. Input range: AI1 voltage and current range:
010V, 020mA
2. Input impedance: 20kΩ during voltage input;
250Ω during current input
3. Voltage or current input is set through the
jumper.
4. Resolution ratio: When 10V corresponds to
50Hz, the min. resolution ratio is 5mV
5. Deviation: ±1% when the input reaches full
the measurement range at 25°C
AO1
Analog output 1
1. Output range: 010V voltage or 020mA
current
2. Voltage or current output is set through the
jumper.
3. Deviation: ±1% when the input reaches full
the measurement range at 25°C.
Relay output
PRO1A
NO contact of relay
1
1. Contact capacity: 2A/AC250V, 1A/DC30V
2. Unable to function as high frequency switch
output
PRO1C
Common contact of
relay 1
PRO2A
NO contact of relay
2
PRO2C
Common contact of
relay 2
Communication
485+
RS485
communication
terminal
RS485 communication port, which can be set
as the master or slave through the Auto
Station. It is differential signal output. Whether
to connect the 120Ω resistor of RS485 is set
through the jumper.
485-
For details about the operation of programmable expansion cards, see the frequency inverter ST600
series AutoStation programmable card manual.