Frequency Inverter ST600 Series High-Performance Multifunction VFD Expansion cards
-328-
State indicators
The EtherNet/IP communication card provides four LED indicators and four net port indicators to
indicate its states.
The card is shaking hands with the VFD.
The card and VFD communicate normally.
The card and VFD communicate improperly.
The communication between the card and PLC is online
and data interchange is allowed.
IP address conflict between the card and PLC.
The communication between the card and PLC is offline.
Failed to set up I/O between the card and PLC.
Incorrect PLC configuration.
The card failed to send data to the PLC.
The connection between the card and PLC timed out.
Link indicator, indicating successful Ethernet connection.
Link indicator, indicating Ethernet connection not
established.
ACK indicator, indicating data interchange being
performed.
ACK indicator, indicating data interchange not be
performed.
Electrical wiring
The EtherNet/IP communication card provides standard RJ45 ports and supports the linear, star, and
ring topologies. The following three figures show the electrical wiring diagrams.
Use CAT5, CAT5e, and CAT6 network cables for electrical wiring. When the communication distance
is greater than 50 meters, use high-quality network cables that meet the high-quality standards.
Figure A-12 Electrical wiring diagram for a linear topology
Master
(PLC)
Slave 1
CN2 CN1
Slave 2
CN2 CN1
Slave n
CN2 CN1
Figure A-13 Electrical wiring diagram for a star topology