Frequency Inverter ST600 High-Performance Multifunction Series VFD Optional peripheral
accessories
-360-
Figure D-2 Power cable arrangement
Power cable arrangement
Multiple double-shielded twisted-pair cables
Multiple shielded twisted-pair cables
For low-voltage digital signals, double-shielded cables are recommended, but shielded or unshielded
twisted pairs (as shown in figure b) also can be used. For frequency signals, however, only shielded
cables can be used.
Relay cables need to be those with metal braided shield layers.
Keypads need to be connected by using network cables. In complicated electromagnetic environments,
shielded network cables are recommended.
Note: Analog signals and digital signals cannot use the same cables, and their cables must be
arranged separately.
Do not perform any voltage endurance or insulation resistance tests, such as high-voltage insulation
tests or using a megameter to measure the insulation resistance, on the VFD or its components.
Insulation and voltage endurance tests have been performed between the main circuit and chassis of
each VFD before delivery. In addition, voltage limiting circuits that can automatically cut off the test
voltage are configured inside the VFDs.
Note: Check the insulation conditions of the input power cable of a VFD according to the local
regulations before connecting it.
Table D-1 Recommended cable dimensions for standard model VFDs
Product model
Recommended cable size (mm²)
Screw
R, S, T U, V,
W
PE
P1 (+)
PB, (+) (-)
Terminal
screw
Tightening
torque
(Nm)
ST600-1R5G3
1.0
1.0
1.0
1.0
M4
1.21.5
ST600-2R2G3
1.0
1.0
1.0
1.0
M4
1.21.5
ST600-004G3
1.5
1.5
1.5
1.5
M4
1.21.5
ST600-5R5G3
2.5
2.5
2.5
2.5
M5
22.5
ST600-7R5G3
4
4
4
4
M5
22.5
ST600-011G3
6
6
6
6
M5
22.5
ST600-015G3
10
10
10
10
M5
22.5
ST600-018G3
10
10
10
10
M5
22.5
ST600-022G3
10
10
10
10
M6
46
ST600-030G3
16
16
116
16
M6
46
ST600-037G3
25
16
25
25
M6
46
ST600-045G3
25
16
25
25
M8
911
ST600-055G3
35
16
35
35
M8
911
ST600-075G3
50
25
50
50
M8
911

Table of Contents