Chapter 2 — Site Requirements Environmental Requirements
September 2022 Site Preperation Guide—Spectra T200, T380, and T680 Library
20
Ethernet Network Connections
Spectra Logic recommends providing the following Ethernet network
connectivity for the library:
Fibre Channel Connections
The Fibre Channel interface in the robotic interface module and direct-
attach tape drives support the Fibre Channel Protocol (FCP). Connecting
RIMs and direct-attach Fibre Channel tape drives to the host network
requires multimode optical cables with dual LC connectors.
For detailed information on connectivity for drives and interface
controllers, see Interface Specifications on page 40.
ENVIRONMENTAL REQUIREMENTS
The site where the library is operated must meet the environmental
requirements described in Environmental Specifications on page 38 to
ensure successful operation of the library. In addition, consider the
following:
Connection Type Description
Direct internet
access
A direct internet connection is recommended so that you
can access the library’s BlueScale software remotely and
download BlueScale updates directly to the library.
Email access Access to an email gateway is required to use the library’s
automated monitoring and technical support features.
BlueScale Vision
camera access
The camera requires a separate Ethernet connection. Using a
shielded cable is required in order to comply with EMC
requirements.
Requirement Description
Air Flow
Air flow through the library is from front to back. Make sure
that cold and hot (airflow in and airflow out) aisle hardware is
positioned appropriately for the library installation location.
Air Quality The library contains an air filter that keeps the inside of the
library free from particulates that might contaminate its
components. Regular inspection and replacement of the air
filter is necessary to keep the library functioning at optimal
levels. Spectra Logic recommends that the filter be inspected
at least once every three months and replaced as frequently
as necessary. Spare filters are available from Spectra Logic
(see Contacting Spectra Logic on page 6).
Fire Protection Spectra Logic recommends that the library be installed close
to your data center’s fire suppression equipment, if present.