Chapter 3 — Installation Preparation Service Access Requirements
September 2022 Site Preperation Guide—Spectra T200, T380, and T680 Library
25
SERVICE ACCESS REQUIREMENTS
A minimum of 24 inches (61 cm) of access clearance is required at the front
and back of the library. For ease of access, Spectra Logic recommends a
working area of at least 36 inches (91 cm) of access clearance.
Because the
library is most easily serviceable from the right side, an additional 36 inches
(91 cm) of access clearance on the right side of the library is highly
recommended.
Allowing 36 inches (91 centimeters) of work space on both
the right and left sides of the library provides the best service access.
Spectra T200 and T380 Figure 3 shows the recommended access clearance
for these libraries. An additional clearance of at least 70 inches (178 cm) in
front is required when installing or removing the library from the rack.
Figure 3 A top view of recommended service access dimensions for the T200
and T380 libraries.
TAP
17.5 inches
(44.5 cm)
36 inches
(91 cm)
Height
T380: 49 in. (125 cm)
41 inches
(105 cm)
Overall depth
9.5 feet
(3.0 m)
T200: 35 in. (89 cm)
36 inches
(91 cm)
36 inches
(91 cm)