6.3 Commissioning - Quick set-up
This section allows the user to carry out the minimum commissioning necessary to operate
the system.
It accepts the defaults set in the factory, so will only work if the original default settings have
not been altered. See the default settings in Section 10, Technical information, to confirm.
Settings can then be tailored to suit the individual requirements of the customer / application
if required.
Warning: - It is essential that you comply with National / Local regulations and
Guidance notes, and the boiler manufacturer's recommendations. It is imperative
that the settings you have accepted will allow the boiler to operate in a safe manner.
This procedure assumes a Pt100 temperature sensor is fitted to the system.
Parameter Action
CAL
Enter actual water TDS or conductivity to calibrate product and
press the
OK
button to enter run mode.
DURATION
Enter time (S) for the bottom blowdown valve to be open and
press the
OK
button to enter run mode.
SET POINT
Set to TDS at which blowdown valve is to open and press
OK
.
ALARM
Set to TDS at which the alarm is to operate and press
OK
(must be higher
than SP).
Test the system to ensure that it is working correctly.