10.8.4 OUTPUT MENU
CLEAN - DRIVE (Action on blowdown / solenoid valve)
Ranges STANDARD or PULSED - 10 sec open, 20 sec closed
Default STANDARD
CLEAN - DURATION (Time to clean probe)
Ranges 0 – 99 seconds or 0 – 9 seconds (If purge time > 0)
Default 20 (9 seconds (If purge time > 0))
Resolution (steps) 1
Units Seconds
CLEAN - INTERVAL (Time between probe cleaning)
Only available if CLEAN - DURATION is greater than 0 seconds.
Ranges 1 – 99
Default 12
Resolution (steps) 1
Units Hours
CLEAN
Only available if CLEAN - DURATION is greater than 0 seconds.
Ranges
PULSED - 1 second on, 1 second off, or CONSTANT
(for CP32 already fitted with a pulse circuit)
Default PULSED
RETRANS – 0 or 4 mA (Lowest output signal)
Ranges 0 mA or 4 mA
Default 4 mA
Units mA
RETRANS – SET – 0 / 4 mA (Set PV to correspond to 0 or 4 mA)
Ranges 0 – FSD
Default 0
Resolution (steps) 0.1% FSD
Units µS / cm or ppm