IM-P323-32
CTLS Issue 5
32
SX80 and SX90 Quickstart Guide
3.4.4.5 Power supply
8
Ensure that you have the correct supply for your controller:
1. Check order code of the controller supplied.
2. Use copper conductors only.
3. The power supply input is not fuse protected. This should be provided
externally.
Safety requirements for permanently connected equipment state:
- A switch or circuit breaker shall be included in the building installation.
- It shall be in close proximity to the equipment and within easy reach of
the operator.
- It shall be marked as the disconnecting device for the equipment.
Note: a single switch or circuit breaker can drive more than one
instrument:
- High voltage supply: 100 to 240 Vac, -15%,
+10%, 48 to 62 Hz SX80 6 Watts.
- SX90 9 W. Recommended external fuse
ratings are: - Fuse type: T rated 2 A 250 V.
L
N
Line
Neutral