SX80 and SX90 Quickstart Guide
To re-enter Quick Code configuration mode
If you need to re-enter the 'Quick Conguration' mode this can always be
done by powering down the controller, holding down the button, and
powering up the controller again.
You must then enter a pass code using the or buttons. In a new
controller the pass code defaults to 4. If an incorrect pass code is entered
you must repeat the whole procedure.
To adjust the Set Point
(Target temperature/pressure)
In the HOME display:-
Press the button to raise the Set Point.
Press the button to lower the Set Point.
The new Set Point is entered when the button is released and is indicated
by a brief ash of the display.
4.2 Operator Level 2
Parameters are available in deeper levels of access protected by security
codes.
Level 2 Parameters are typically used when commissioning the controller.
To select Level 2:
1. From any display press and hold the button until Lev1 is shown.
2. Release the button and press the or buttons to choose
Lev2 (Level 2).
3. Press the or buttons to enter the pass code. Default = 2.