60
 
the type of alarm (see Table 6), if we have several alarms at the same time, the yellow LED indicates the alarm with higher priority, 
the priority sequence is defined on table as follows: 
 
 
Display  Priority  Alarm  Action 
yellow 
 
1 
Rotor is blocked 
Wait or deblock the 
shaft 
LED 1 red + LED 4 
yellow 
 
2 
Supply voltage 
too low 
Control the supply 
voltage 
LED 1 red + LED 3 
yellow 
 
3 
Electrical error 
Control the supply 
voltage or replace 
the pump 
Table 7 - Alarms 
 
21.2. Pump Wilo 15-130/7-50 
The Wilo 15-130/7 50 circulator pump consists of: 
1. Pump housing with screwed connections  
2. Glandless motor 
3. Condensate drain openings (4x around circumference) 
4. Housing screws 
5. Control module 
6. Rating plate 
7. Operating button for pump adjustment 
8. Run signal/fault signal LED 
9. Display of selected control mode 
10. Display of selected characteristic curve (I, II or III) 
 
 
Figure 60 - Pump Wilo 
Installing the pump 
Observe the following points when installing the pump (Figure 61): 
- Note the direction arrow on the pump housing (1). 
- Install glandless motor (2) horizontally, without mechanical tension. 
- Place gaskets in the screwed connections. 
- Screw on threaded pipe unions. 
- Use an open-end wrench to secure the pump against twisting and screw tightly to piping. 
- Re-mount the thermal insulation shell if required. 
Figure 61 – Installing the pump