27
CAUTION:
The M2B controller automatically defaults to a 250
o
F (121.1
o
C)
set-stop limit, water temperature control unit (TCU) configuration. All
special configurations. i.e. 4-20 MA scaling, will be lost. Please record
menu variables before performing a factory default. If you have an oil TCU,
the controller must be re-configured for a high temperature 550
o
F
(287.7
o
C) set-stop limit.
High Temperature Oil
Re-configuration
Depress and hold the
UP
and
ENTER
keypads simultaneously for five
(5) seconds to enter the secure menu.
•“



” will appear in the left display and “
.
..
.
” will appear in the right
display.
Depress the
INDEX
keypad until “


)
))
)
” appears in the left display and



” appears in the right display.
Depress the
UP
arrow until “



” appears in the right display.
Depress the
DOWN
and
ENTER
keypads simultaneously to enter the
parameter.
Both the displays will flash “
&&
&&&&
&&
” then “



“ indicating the re-boot is
complete.
Depress the
SET POINT
keypad for short cut to the run mode, or, wait
thirty (30) seconds for auto exit to run mode.
S
P
P
S
P
S
P
S
P
RUN