EasyManua.ls Logo

Structural Concepts FSI856R - CAREL CONTROLLER: Summary Table of Operating Parameters (after Programming Key)

Structural Concepts FSI856R
36 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
CODE PARAMETER UOM* TYPE MINIMUM MAXIMUM DEFAULT
/c1 Calibration of probe 1 °C/°F C -20 20
/c2 Calibration of probe 2 °C/°F C -20 20
St Temperature set point °C/°F F r2 r1
rd Control delta °C/°F F 20 0.1
dl Interval between defrosts hours F 0 250
dt1 End defrost temperature, evaporator °C/°F F -50 200
dP1 Maximum defrost duration, evaporator min F 1 250
d6 Display on hold during defrost - C 0 2
dd Dripping time after defrost min F 0 15
d/1 Display of defrost probe 1 °C/°F F - -
/5
Select Celsius (°C) or Fahrenheit (°F)
flag C 0 1
35
For Case
Specific
Defaults
See Serial
Label
Located
Near
Electrical
Access
On Your
Case.
For
Additional
Technical
Information
Call
Structural
Concepts
Technical
Service
Dept. at
1(800)
433.9489
* Unit Of Measure
Read And Save These Instructions - Page 3 of 3
Integrated Electronic
Microprocessor Controller
Summary Table of Operating Parameters

Table of Contents

Related product manuals