EasyManuals Logo

Studer RCC-03 User Manual

Studer RCC-03
104 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #89 background imageLoading...
Page #89 background image
Studer Innotec SA
RCC-02/-03
User manual V4.4.0 85
Level
User
ref.
Parameter
Unit
12
24
48
Mod.
value
Factory
Min
Max
Factory
Min
Max
Factory
Min
Max
Expert
1171
Floating duration before reduced floating
days
1
0
31
1
0
31
1
0
31
Expert
1172
Reduced floating voltage
Vdc
13.2
9.5
18
26.4
19
36
52.8
37.9
72
Expert
1454
Periodic absorption phase
Expert
1173
Periodic absorption allowed
No/Yes
No
-
-
No
-
-
No
-
-
Expert
1174
Periodic absorption voltage
Vdc
14.4
9.5
18
28.8
19
36
57.6
37.9
72
Expert
1175
Reduced floating duration before periodic
absorption
days
7
0
31
7
0
31
7
0
31
Expert
1176
Periodic absorption duration
hours
0.5
0
10
0.5
0
10
0.5
0
10
Expert
1186
INVERTER
Basic
1124
Inverter allowed
Yes/No
Yes
-
-
Yes
-
-
Yes
-
-
Expert
1286
AC Output voltage
Vac
230
110
280
230
110
280
230
110
280
Expert
1548
AC voltage increase according to battery
voltage
No/Yes
No
-
-
No
-
-
No
-
-
Expert
1560
Max AC voltage increase with battery voltage
Vac
10
5
15
10
5
15
10
5
15
Expert
1112
Inverter frequency
Hz
50
45
65
50
45
65
50
45
65
Expert
1536
Inverter frequency increase when battery full
No/Yes
No
-
-
No
-
-
No
-
-
Expert
1549
Inverter frequency increase according to battery
voltage
No/Yes
No
-
-
No
-
-
No
-
-
Expert
1546
Max frequency increase
Hz
4
0
10
4
0
10
4
0
10
Expert
1534
Speed of voltage or frequency change in
function of battery
0
-4
1
0
-4
1
0
-4
1
Expert
1420
Standby and turn on
Basic
1187
Standby level
%
10
0
100
10
0
100
10
0
100
Expert
1189
Time delay between standby pulses
sec
0.8
0.2
10
0.8
0.2
10
0.8
0.2
10
Expert
1188
Standby number of pulses
1
1
10
1
1
10
1
1
10
Expert
1599
Softstart duration
sec
0
0
1
0
0
1
0
0
1
Expert
1438
Solsafe presence Energy source at AC-Out
side
No/Yes
No
-
-
No
-
-
No
-
-
Expert
1197
AC-IN AND TRANSFER
Expert
1128
Transfer relay allowed
Yes/No
Yes
-
-
Yes
-
-
Yes
-
-
Expert
1580
Delay before closing transfer relay
min
0
0
30
0
0
30
0
0
30
Basic
1126
Smart-Boost allowed
Yes/No
Yes
-
-
Yes
-
-
Yes
-
-
Inst.
1607
Limitation of the power Boost
%
100
0
100
100
0
100
100
0
100
Basic
1107
Maximum current of AC source (Input limit)
Aac
32
2
50
32
2
50
32
2
50
Expert
1471
Max input current modification
Expert
1566
Using a secondary value for the maximum
current of the AC source
No/Yes
No
-
-
No
-
-
No
-
-
Expert
1567
Second maximum current of the AC source
(Input limit)
Aac
16
2
50
16
2
50
16
2
50
Expert
1527
Decrease max input limit current with AC-In
voltage
No/Yes
No
-
-
No
-
-
No
-
-

Table of Contents

Other manuals for Studer RCC-03

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Studer RCC-03 and is the answer not in the manual?

Studer RCC-03 Specifications

General IconGeneral
BrandStuder
ModelRCC-03
CategoryExtender