MODBUS Protocol 91
E500 Series Universal Low-Power Inverter
(3). Read current running frequency, output current, inverter response frequency
50.0Hz and output current 1.1A of inverter.
Main machine request:
Slave
machine
address
Function
code
Register initial address Number of registers CRC CHECK
High Low High Low Low High
01 03 D0 00 00 02 FC CB
Slave machine response:
Slave
machine
address
Function
code
Number of
reading bytes
1st register data 2nd register data CRC CHECK
High Low High Low Low High
01 03 04 01 F4 00 0B FB FA
(4). Start 1# inverter in FWD running condition and set inverter running
Frequency as 40. 0Hz.
Main machine request:
Slave
machine
address
Function
code
Register
initial
address
Number of
registers
Number
of content
bytes
1st
register
data
2nd register
data
CRC
CHECK
High Low High Low High Low High Low Low High
01 10 10 01 00 02 04 00 01 01 90 AF 9F
Slave machine response:
Slave
machine
address
Function
code
Register initial address Number of registers CRC CHECK
High Low High Low Low High
01 10 10 01 00 02 14 C8