56
Figure Step
3. When the surface is clean and dry, paint the base
material revealed parts with zinc primer (or other local
primers with the same function) for protection. The paints
should cover the revealed primer completely.
4. Paint the scratched parts by banister brush when the
primer is dry, and make sure the painting is as uniform as
possible.
Check the protective paint on the module surface for peeling off. re-paint the MV
Station surface if necessary.
Re-spray the protective paint every 5 years to the MV Station surface.
9.5 Replace the Fuse of LV Cabinet
Disconnect the MV load switch before servicing components in the LV cabinet.
9.5.1 Replace SPD Fuse
step 1 Open the SPD fuse holder in the LV cabinet (fuse position, see "3.3.2 LV Cabinet").
step 2 Remove the fuse to be replaced and install a new one.
9 Routine Maintenance System Manual