109
Parameter SG5.0RT SG6.0RT
Input (DC)
Recommended max. PV in-
put power
7.5 kWp 9.0 kWp
Max. PV input voltage 1100 V
*
Min. PV input voltage /
Start-up input voltage
180 V / 180 V
Nominal input voltage 600 V
MPP voltage range 160 V–1000 V
No. of independent MPP
inputs
2
No. of of PV strings per
MPPT
1 / 1
Max. PV input current 25 A (12.5 A / 12.5 A)
Max. DC short-circuit
current
36 A (18 A / 18 A) for "AU"
32 A (16 A / 16 A) for others
32 A (16 A / 16 A)
Output (AC)
Nominal AC power (@ 230
V, 50 Hz)
5000 W 6000 W
Max. AC output power 5000 VA for "AU", "BE",
"DE", 5500 VA for others
6000 VA for "AU", "BE",
"DE", 6600 VA for others
Rated AC output apparent
power
5000 VA for "AU", "BE",
"DE", 5500 VA for others
6000 VA for "AU", "BE",
"DE", 6600 VA for others
Max. AC output current 7.6 A for "AU", 8.3 A for
others
9.1 A for "AU", 10 A for
others
Nominal AC voltage
3 / N / PE, 220 V / 380 V
3 / N / PE, 230 V / 400 V
3 / N / PE, 240 V / 415 V
AC voltage range 180 V–276 V / 311 V–478 V
Nominal grid frequency /
Grid frequency range
50 Hz / (45 Hz–55 Hz)
60 Hz / (55 Hz–65 Hz)
Harmonic (THD) < 3 % (at rated power)
Power factor at nominal
power / Adjustable power
factor
> 0.99 / 0.8 leading 0.8 lagging
Feed-in phases / connec-
tion phases
3 / 3–PE
Efficiency
Max. efficiency 98.40 %