EasyManuals Logo

Sungrow SG50CX-P2 User Manual

Sungrow SG50CX-P2
150 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #133 background imageLoading...
Page #133 background image
123
Restart the inverter only after removing the fault that impairs safety performance.
As the inverter contains no component parts that can be maintained, never open
the enclosure, or replace any internal components.
To avoid the risk of electric shock, do not perform any other maintenance opera-
tions beyond this manual. If necessary, contact your distributor first. If the problem
persists, contact SUNGROW. Otherwise, the losses caused is not covered by the
warranty.
Touching the PCB or other static sensitive components may cause damage to the
device.
Do not touch the circuit board unnecessarily.
Observe the regulations to protect against electrostatic and wear an anti-static
wrist strap.
9.2.2 Quick Shutdown
The PV system can perform a quick shutdown, reducing the output voltage of strings to be-
low 30 V within 20s.
Triggering methods of quick shutdown:
Method 1: Turn off the AC circuit breaker between the inverter and the grid.
Method 2: Connect DI and PGND in COM2 port to trigger quick shutdown. Disconnect DI
and PGND to exit the quick shutdown mode.
The quick shutdown is not supported if optimizers are configured for some PV
modules.
Please check regularly whether the quick shutdown function is normal.
User Manual 9 Troubleshooting and Maintenance

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Sungrow SG50CX-P2 and is the answer not in the manual?

Sungrow SG50CX-P2 Specifications

General IconGeneral
Rated Power50 kW
Max. DC Voltage1100 V
MPPT Voltage Range200 V - 1000 V
Max. Input Current per MPPT26 A
Number of DC Input Terminals per MPPT2
Rated AC Output Power50 kW
Max. AC Output Power55 kW
AC Nominal Voltage400 V
AC Voltage Range310 V - 480 V
AC Grid Frequency50 Hz / 60 Hz
Grid Frequency Range45 Hz - 55 Hz / 55 Hz - 65 Hz
Total Harmonic Distortion<3%
DC SwitchYes
Protection ClassI
Cooling MethodSmart Forced Air Cooling
Protection DegreeIP66
Maximum Efficiency98.7%
TopologyTransformerless
Power Factor at Rated Power0.8 leading to 0.8 lagging
Operating Temperature Range-25°C to +60°C
CommunicationRS485, Ethernet

Related product manuals