SINGLE PHASE HI 3.6/5kW | User Manual16
Inverter hanging plate installation
4.4. Battery Connection
For safe operation and compliance, a separate DC over-current protector or disconnect device is required
between the battery and the inverter. Switching devices may not be required in some applications, but
over-current protectors are still required. Refer to the typical amperage in the table below for the required
fuse or circuit breaker size.
Model Wire Size Cable (mm
2
) Torque value (max.)
3.6kW / 5kW 2AWG 25 5.2N.m