EasyManua.ls Logo

Swegon CONDUCTOR W1 - Page 48

Swegon CONDUCTOR W1
63 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5 : 48
Service
Display image Description
P_1046 18 C
Night cool temp set point
min 10 max 20
Indicates the temperature
setpoint applicable to the Night
cool function.
P_1047 80 %
Night cool flow SA %
min 50 max 100
Indicates the supply airflow for
“night cool”.
P_1048 80 %
Night cool flow EA %
min 50 max 100
Indicates the extract airflow for
“night cool”.
P_1049 5000
P term Cooling Scale 1:100
min 1 max 10000
Indicates the value for P for
cooling. A high value denotes
faster control. A low value
denotes slower control.
P_1050 10
I term Cooling Scale 1:100
min 1 max 10000
Indicates the value for I for
cooling. A high value denotes
faster control. A low value
denotes slower control.
P_1051 5000
P term Heating Scale 1:100
min 1 max 10000
Indicates the value for P for
heating. A high value denotes
faster control. A low value
denotes slower control.
P_1052 10
I term Heating Scale 1:100
min 1 max 10000
Indicates the value for I for
heating. A high value denotes
faster control. A low value
denotes slower control.
P_1053 23
TC_Normal
min 15 max 30
Switch in cooling for normal
operation.
P_1054 21
TH_Normal
min 15 max 30
Switch in heating for normal
operation.
P_1055 25
TC_Economy
min 10 max 30
Switch in cooling for economic
operation.
P_1056 19
TH_Economy
min 10 max 30
Switch in heating for economic
operation.

Related product manuals