5 : 47
Service
Display image Description
P_1029 2 K
Boost at temp. over setpoint (K)
min 1 max 10
Indicates by how much the
room temperature actual value
should rise above the setpoint
in order for the controller to
switch from AUTO to BOOST.
P_1034 1
Timer function available?
min 0 max 1
Indicates whether time-adjusted
fl ow boost is accessible.
(0=No, 1=Yes)
P_1035 5 min
Timer function time (min)
min 1 300
Indicates how long the time-
adjusted fl ow boost should
be on ON when occupancy is
activated
P_1038 16 C
Room unit’s min set point
min 0 max 20
The lowest possible room
temperature setpoint for the
MAN operating mode
P_1039 28 C
Room unit’s max set point
min 25 max 50
The highest possible room
temperature setpoint for the
MAN operating mode.
P_1040 10 %
Room unit’s min air flow
min 5 max 50
The lowest possible airflow
setpoint for the MAN operating
mode.
P_1041 100 %
Room unit's max air flow
min 50 max 100
The highest possible airflow
setpoint for the MAN operating
mode.
P_1042 1 K
Boost temp. below setpoint (K)
0 max 10
Indicates how much the current
room temperature should differ
from the setpoint in order for
the controller to switch from
BOOST to AUTO.
P_1043 20 %
Economy flow SA %
min 0 max 100
Indicates the supply airflow for
ECON.
P_1044 20 %
Economy flow EA %
min 0 max 100
Indicates the extract airflow for
ECON.
P_1045 480 min
RU back to auto state
min 0 max 1200
Indicates how long time after
the latest manual adjustment of
room temperature or airfl
ow that the controller should
return to AUTO.
(0=Is not used)