Service
Display image Description
P_1018 0 mV
SA mV at 0% output
min 0 max 5000
Offset voltage for 0% supply
airflow.
(Dissolution=50mV)
P_1019 10000 mV
SA mV at 100% output
min 5000 max 10000
Offset voltage for 100% supply
airflow.
(Dissolution=50mV)
P_1020 0 mV
EA mV at 0% output
min 0 max 5000
Offset voltage for 0% extract
airflow.
(Dissolution=50mV)
P_1021 10000 mV
EA mV at 100% output
min 5000 max 10000
Offset voltage for 100% extract
airflow.
(Dissolution=50mV)
P_1022 1
Economy mode available?
min 0 max 1
Indicates whether the Economy
mode is available.
0 = No
1 = Yes
P_1023 1
ActuatorCool 1=NC,2=0-10V,3=NO
min 1 max 3
Indicates which sort of valve
actuator is installed in the
cooling water circuit.
(1=24V-NC, 2=0-10V, 3=24V-
NO)
P_1024 1
ActuatorHeat 1=NC,2=0-10V,3=NO
min 1 max 3
Indicates which sort of valve
actuator is installed in the
heating water circuit.
(1=24V-NC, 2=0-10V, 3=24V-
NO)
P_1025 0
Window 0=NP,1=NC,2=NO
min 0 max 2
Indicates whether a window
contact is installed and if so
how it is installed.
0 = No contact installed
1 = Normally closed
2 = Normally open
P_1026 0
Occupancy 0=NP,1=NC,2=NO
min 0 max 2
Indicates whether a presence
detector is installed and if so
how it is installed.
0 = No contact installed
1 = Normally closed
2 = Normally open
P_1027 5000
P term Change over
min 1 max 10000
Indicates the value for P for the
Change Over function. A high
value denotes faster control.
A low value denotes slower
control.
P_1028 50
I term Change over
min 1 max 10000
Indicates the value for I for the
Change Over function. A high
value denotes faster control.
A low value denotes slower
control.