F • 22 W Remote control voltage output FP-+24V short-circuit (voltage less than 18V)
C • Performance-component failure
R • Check wiring. Switch on and off several times. If the fault still exists, send in frequency inverter for
repair.
F • 23 W Remote control voltage output FP-+7V short-circuit (voltage less than 5.5V)
C • Performance-component failure
R • Check wiring. Switch on and off several times. If the fault still exists, send in frequency inverter for
repair.
F • 24 W Inadmissible code for motor coding
C • Motor coding input set to a higher code number than motors configured in P102-motor coding, e.g.
coding input is 4 and only 3 motors configured in P102
R • Check signal values at X7 (also see P20-motor code) or parameter P102-motor coding
F • 25 W Motor coding changed while motor running
C • Motor coding input at X7 changed while motor running
R • Check signal values at X7, they may not change while the motor is running (also see P20-motor code)
F • 26 W Unused motor parameter memory for motor coding
C • The value at motor coding input X7 indicates an empty parameter memory M1...M32
R • Check signal values at X7 (also see P20-motor code) or store parameter for corresponding motor
F • 42 E Flash program memory faulty
C • Hardware failure
R • Switch on and off several times. If the fault still exists, send in frequency inverter for repair: motor
can still be operated.
F • 43 E EEPROM faulty in self-test (data memory)
C • Hardware failure
R • Switch on and off several times. If the fault still exists, send in frequency inverter for repair: motor
can still be operated.
F • 45 W Watchdog reset on motor control
C • Strong EMC interference on motor control circuit board
R • Warning indication is automatically reset after 10 seconds and motor continues to run
F • 47 E Motor type from P90-motortype not supported
C • Parameter P90-motortype configured incorrectly
R • Check the software and firmware versions. Set parameter P90-motortype.
F • 52 E Fault in DC-converter during self-test
C • Performance-component failure
R • Switch on and off several times. If the fault still exists, send in frequency inverter for repair.
F • 53 E Short circuit or earth leakage in DC-converter
C • Performance-component failure
R • Check wiring. Switch on and off several times. If the fault still exists, send in frequency inverter for
repair.