8.15 Device Parameters, Remote Control
P102 motor coding
By means of this parameter, the motor coding is switched on and the number of motors used is input (see
chapter 4.5 Motor coding).
Only the actually selected motor parameters sets M1…M32 will be analyzed.
P104 FF1
Value of the fixed frequency FF1 which can be selected via the remote control.
By means of parameter P8-speed display, this parameter can be changed from frequency display to speed
display, the number of motor poles P96-no. of poles being taken into account.
Minimum value: 50 Hz
Maximum value: 4,000 Hz
Factory setting: 100 Hz
P105 FF2
Value of fixed frequency FF 2
Minimum value: 30 Hz
Maximum value: 4,000 Hz
Factory setting: 100 Hz
P106 FF3
Value of fixed frequency FF3
Minimum value: 30 Hz
Maximum value: 4,000 Hz
Factory setting: 100 Hz
P110 input IN1
Function of the digital input IN1
Values: Description
Off Input has no function
/Stop (24 V = Start release, 0 V = Stop, for Start is P111-input IN2 to
be configured to start impulse
Start/Stop 24 V = Start, 0 V = Stop
P111 input IN2
Function of the digital input IN2
Values: Description:
Off Input has no function
Counter-clockwise CCW rotation (24 V = CCW)
Reset Reset (pulse at 24 V = trigger reset)
Start impulse An impulse of +24 V starts the inverter, after which the input can return to 0 V,
whereby the inverter remains in the start condition. To stop, configure input IN1
with P110-input IN1 to “Stop”, and bring it to 0 V
Motor coding Frees up the input for the motor coding, the input has the value Bit4
P112 input IN3
Function of the digital input IN3
Values: Description:
Off Input has no function
Counter-clockwise CCW rotation (24 V = CCW)
Reset Reset (pulse at 24 V = trigger reset)
Motor coding Frees up the input for the motor coding, the input has the value Bit0