Operator’sGuideannex17
Instructionsforuseofthemachinesectionkinthismanual
Instructionsaboutadjustmentandmaintenancesectionrinthismanual
Safetyduringadjustmentandmaintenancesections
f.Employeesinchargeofoperation/control/maintenance
Theunitisabletooperatefullyautomaticallywhentheinstaller hasstarted,adjustedandhandedoverthe
faultlessunittothestaffthattakescareofoperation,controlandmaintenance.
f1.Employeesthattakecareofordinaryoperation
IndicationsofoperationstatusaswellasindicationoffaultsarevisibleinthedisplayandontheLED’sof
thehandterminal.Theemployeescanenternewparametersinthecontroller viathebuttonsonthehand
terminal.ThealternativeisthatthecontrollerisconnectedtoaBMSsystem
withtheabilitytoselectnew
parametersviaPC,tablet,SmartPhoneormobilephone.
g.Intendeduseandrangeofapplications
Theairhandlingunitsareintendedforthetransportandtreatmentofairbetween‐40°Cand+40°C
Theunitsareexclusivelyforcomfortventilationandnotforairthatcausesseverecorrosiontogalvanized
steelandtocopperandaluminum.Theunitsarenotforenvironmentsthatexceed
thecorrosionclassC4
accordingtoENISO129442.
Intendedapplicationsfortheunitsare:
Offices,teachingrooms,hotels,shops,homesandsimilarcomfortzones.
h.Unintendeduseandmisuseinappropriateapplicationsforthe
machine
TheairhandlingunitsarenotsuitablefortransportofairwithriskofexplosionandwithExClassification.
DonotinstalltheunitsinExareasatall.
Donotinstallunitsoutdoorsunlesstheunitsare constructedforoutdoorinstallation.Unitsnotsuitablefor
outdoorinstallationareunitswithout
roofandunitswithcabinetinstalledontheunit(thecabinetis
installedinsidetheunitforoutdoorinstallation).
TheunitsarenotforenvironmentsthatexceedthecorrosionclassC4accordingtoENISO129442,andthe
unitsarenotfortransportofsolidparticles.
Notintendedapplications
fortheunitsare:
Kitchenextraction,swimmingpools,offshore,Exareas,dryingofwashedclothes.
Donotusetheunitwithpartlyfinishedductsystems.Donotusetheunitforventilationofthebuildingsite
untiltheunitisproperlyprovidedwithguards.
h.1Airhandlingunitinoperation
Thepressuredifferencebetweeninteriorandexterioroftheunitmustnotexceed2000PafortheDV10
anduptoDV150(includingDV150),and1500PaforDV190andDV240.
Beforestartupoftheunitallducts,guardsandallprotectivedevicesmustbe
mountedtopreventany
accesstorotatingfanimpellers.Allinspectiondoorsmustbeclosedandlockedwhentheunitisin
operation.
Donotusetheunitwithoutfilters.