23
Operator’sGuide–annex17
Instructionsforuseofthemachine–sectionkinthismanual
Instructionsaboutadjustmentandmaintenance–sectionrinthismanual
Safetyduringadjustmentandmaintenance–sections
f.Employeesinchargeofoperation/control/maintenance
Theunitisabletooperatefullyautomaticallywhentheinstaller hasstarted,adjustedandhandedoverthe
faultlessunittothestaffthattakescareofoperation,controlandmaintenance.
f1.Employeesthattakecareofordinaryoperation
IndicationsofoperationstatusaswellasindicationoffaultsarevisibleinthedisplayandontheLED’sof
thehandterminal.Theemployeescanenternewparametersinthecontroller viathebuttonsonthehand
terminal.ThealternativeisthatthecontrollerisconnectedtoaBMSsystem
withtheabilitytoselectnew
parametersviaPC,tablet,SmartPhoneormobilephone.
g.Intendeduseandrangeofapplications
Theairhandlingunitsareintendedforthetransportandtreatmentofairbetween‐40°Cand+40°C
Theunitsareexclusivelyforcomfortventilationandnotforairthatcausesseverecorrosiontogalvanized
steelandtocopperandaluminum.Theunitsarenotforenvironmentsthatexceed
thecorrosionclassC4
accordingtoENISO12944‐2.
Intendedapplicationsfortheunitsare:
Offices,teachingrooms,hotels,shops,homesandsimilarcomfortzones.
h.Unintendeduseandmisuse–inappropriateapplicationsforthe
machine
TheairhandlingunitsarenotsuitablefortransportofairwithriskofexplosionandwithEx‐Classification.
DonotinstalltheunitsinEx‐areasatall.
Donotinstallunitsoutdoorsunlesstheunitsare constructedforoutdoorinstallation.Unitsnotsuitablefor
outdoorinstallationareunitswithout
roofandunitswithcabinetinstalledontheunit(thecabinetis
installedinsidetheunitforoutdoorinstallation).
TheunitsarenotforenvironmentsthatexceedthecorrosionclassC4accordingtoENISO12944‐2,andthe
unitsarenotfortransportofsolidparticles.
Notintendedapplications
fortheunitsare:
Kitchenextraction,swimmingpools,off‐shore,Ex‐areas,dryingofwashedclothes.
Donotusetheunitwithpartlyfinishedductsystems.Donotusetheunitforventilationofthebuildingsite
untiltheunitisproperlyprovidedwithguards.
h.1Airhandlingunitinoperation
Thepressuredifferencebetweeninteriorandexterioroftheunitmustnotexceed2000PafortheDV10
anduptoDV150(includingDV150),and1500PaforDV190andDV240.
Beforestart‐upoftheunitallducts,guardsandallprotectivedevicesmustbe
mountedtopreventany
accesstorotatingfanimpellers.Allinspectiondoorsmustbeclosedandlockedwhentheunitisin
operation.
Donotusetheunitwithoutfilters.