EasyManuals Logo

SystemAir Danvent DV User Manual

SystemAir Danvent DV
60 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #23 background imageLoading...
Page #23 background image
23
Operator’sGuideannex17
Instructionsforuseofthemachinesectionkinthismanual
Instructionsaboutadjustmentandmaintenancesectionrinthismanual
Safetyduringadjustmentandmaintenancesections
f.Employeesinchargeofoperation/control/maintenance
Theunitisabletooperatefullyautomaticallywhentheinstaller hasstarted,adjustedandhandedoverthe
faultlessunittothestaffthattakescareofoperation,controlandmaintenance.
f1.Employeesthattakecareofordinaryoperation
IndicationsofoperationstatusaswellasindicationoffaultsarevisibleinthedisplayandontheLED’sof
thehandterminal.Theemployeescanenternewparametersinthecontroller viathebuttonsonthehand
terminal.ThealternativeisthatthecontrollerisconnectedtoaBMSsystem
withtheabilitytoselectnew
parametersviaPC,tablet,SmartPhoneormobilephone.
g.Intendeduseandrangeofapplications
Theairhandlingunitsareintendedforthetransportandtreatmentofairbetween‐40°Cand+40°C
Theunitsareexclusivelyforcomfortventilationandnotforairthatcausesseverecorrosiontogalvanized
steelandtocopperandaluminum.Theunitsarenotforenvironmentsthatexceed
thecorrosionclassC4
accordingtoENISO129442.
Intendedapplicationsfortheunitsare:
Offices,teachingrooms,hotels,shops,homesandsimilarcomfortzones.
h.Unintendeduseandmisuseinappropriateapplicationsforthe
machine
TheairhandlingunitsarenotsuitablefortransportofairwithriskofexplosionandwithExClassification.
DonotinstalltheunitsinExareasatall.
Donotinstallunitsoutdoorsunlesstheunitsare constructedforoutdoorinstallation.Unitsnotsuitablefor
outdoorinstallationareunitswithout
roofandunitswithcabinetinstalledontheunit(thecabinetis
installedinsidetheunitforoutdoorinstallation).
TheunitsarenotforenvironmentsthatexceedthecorrosionclassC4accordingtoENISO129442,andthe
unitsarenotfortransportofsolidparticles.
Notintendedapplications
fortheunitsare:
Kitchenextraction,swimmingpools,offshore,Exareas,dryingofwashedclothes.
Donotusetheunitwithpartlyfinishedductsystems.Donotusetheunitforventilationofthebuildingsite
untiltheunitisproperlyprovidedwithguards.
h.1Airhandlingunitinoperation
Thepressuredifferencebetweeninteriorandexterioroftheunitmustnotexceed2000PafortheDV10
anduptoDV150(includingDV150),and1500PaforDV190andDV240.
Beforestartupoftheunitallducts,guardsandallprotectivedevicesmustbe
mountedtopreventany
accesstorotatingfanimpellers.Allinspectiondoorsmustbeclosedandlockedwhentheunitisin
operation.
Donotusetheunitwithoutfilters.

Table of Contents

Other manuals for SystemAir Danvent DV

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SystemAir Danvent DV and is the answer not in the manual?

SystemAir Danvent DV Specifications

General IconGeneral
BrandSystemAir
ModelDanvent DV
CategoryAir Handlers
LanguageEnglish

Related product manuals