38
k.3Documentationisavailablefordownloadfromhttps://techdoc.systemair.dk
YourlocalSystemaircompanyisabletoprovidethedataorpossiblyaPassword.
k.4Start‐upbyinstaller
Allprotectionandsafetymeasuresmustbemetbeforestart‐upoftheunit.Themainssupplyvoltagemust
alsobecheckedtoo.Themainssupplyvoltagemustbemeasuredatthesupplyterminalsinthecabinet.
k.4.1Checklist,relevantvalues
k.4.1.1Checklistpriortostart‐up
Istheunitassembledcorrectlywithitsfunctionsinthecorrectorder?Seeannex2.
Arethesectionsandductsassembledcorrect?Seeannexi.
Checkthatfansandanti‐vibrationmountsarenotdamagedaftertransportationandinstallation.
Isthe
rotaryexchangerturningfreely?
Aresafetyguardsinstalledcorrectly?
Iftheunitincludesintegratedcooling(DVU),checkwhetheritisinstalledandsupervisedby
qualifiedservicepersonnel.
IftheunitcontainsElectricairheater,makesurethatthesupplyisolatordisconnectswiththeunit.
Ducts‐are
allductsinstalled?
Externalcomponents‐arethevalveandvalvemotorinstalledcorrectly?
Isthecirculationpumpinstalledcorrectly?
Iswaterunderpressureinthecoilandcirculationpump?
Arethepressuretransmittersinstalledandconnectedcorrectly?(Ifthisisasystemwithpressure
transmittersin
theducts)
Mainpowersupply:
o Connectedcorrectly?(3x400V+N+PE)
o Testofsupplyvoltageforactuatorsandcontrolsignal!
o Arecontrolsignalsforactuatorsconnectedcorrectly?
k.4.1.2Switchonpower
Donotstartuntilallsafetyprocedureshavebeencompletedandensurethatinspection
doorsareclosed
andlocked.
Switchonpowerandtheunitshouldbereadyforthestart‐up.
Forstart‐upseetheOperator’sguidefortheSystemaircontrolpanel‐annex 17(thismanualisdelivered
withtheunit–printedonpaperand alsoavailableonthedeliveredDVD).
K.5Adjustmentsanduse
AdjustthefactorysetvaluesforparametersontheSystemairControlPanelorviathesoftwareE‐Toolona
PC.SeetheOperator’sguidefortheSystemaircontrolpanel‐annex17(thismanualisdeliveredwiththe
unit–printedonpaperandalsoavailableonthedeliveredDVD.Further
informationaboutthecontrolleris
availableonthe100pagesintheCorrigoE28UserManualthatisavailableonthedeliveredDVD.
E‐ToolsoftwareisalsoavailableonthedeliveredDVDandfordownloadfromahomepage.
K.6Descriptionoffunctions
K.6.1Remotecontrol
k.6.1.1CommunicationWEB‐master(TCP/IPExoline)toPCandAndroidtelephone

Table of Contents