46
l.8BatteriesforheatingandcoolingtypeDVRDVHDVK,coolingcompressor
l.8.1Extremetemperatures‐heating
Hazards/dangerousarea:
Electricalheatingelementscanachievesurfacetemperatureof500degreeCelsius.
Batteriesandpipesforhotwatercanachieve95degreeCelsius.
Dangerousincident:
AccordingtoISO137321:2006,hereisnodirectriskofburns.(shorttimecontactlesserthan2,5sec).
Claimforreductionofdanger:
No.
l.8.2Extremetemperatures‐cooling
Hazards/dangerousarea:
Evaporatorbatteriesandpipesconnectedtocoolingcompressorcanachieveminus10degreesCelsius.
Dangerousincident:
AccordingtoISO137321:2006,hereisnodirectriskofburns.(shorttimecontactlesserthan2,5sec).
Claimforreductionofdanger:
No.
l.9CoolingcompressorunitstypeDVUDVUC
l.9.1Riskofhightemperature
Hazards/dangerousarea:
Condenserbatteriesandpipescanachievetemperatureof60degreeCelsius.
Dangerousincident:
VurderetudfraISO137321:2006,dererumiddelbartikkerisikoforforbrændinger.(berøringstid2,5sek).
Claimforreductionofdanger:
No.
l.9.2Riskcausedbylightningstrike
Hazards/dangerousarea:
Lightningstrikeclosetothemachine.
Dangerousincident:
Lightningstrikecancreateflashoverbetweenphasesandconductiveparts.Thiscancausefireorthe
overvoltagecanmakeinjuryonpersons
Claimforreductionofdanger:
Installerandusermustbeawareofthefactthatlightningmakesariskthatrequiresinstallationof
overvoltageprotectiondevicestoleadthelightningovervoltagetoanearthleadonasafeway.Theneed
forovervoltageprotectiondevicesdependonwheretheunitis placedinandonthe
building.
Installerandusermusttakecareofthisaccordingtolocalstatutoryrequirements.Overvoltageprotection
devicesarealsodescribedinsectioni.3.3.3ofthismanual
m.Instructionsontheprotectivemeasurestobetakenbyallservice
techniciansduringrepairandmaintenance
Usethebelowmentionedpersonalprotectiveequipmentformaintenance:
Cutresistantglovesforprotectionagainstinjuryfromsharpmetalplateedges.UseCEmarked
glovesforthispurpose.