EasyManua.ls Logo

SystemAir Danvent DV

SystemAir Danvent DV
60 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
49
r.2Recommendedmaintenanceintervals
Function Maintenance Number
peryear
Unitcasing Cleaningoftheunitcasing. 1
Controlofrubbersealsondoorsandbetweensections. 1
Filters Changeondemandbyalarmandalwaysminimumtwiceayear. 2
Controlofrubberseals.Controlofthesystemwithlateral
lockingrailsandhandlesonTIMEandDV10DV150.Controlof
thefilterbankframeswithfastenersonDV190andDV240.
2
Fans Cleaningofallparts. 1
Checkmotorsandbearings 1
Checkthattheimpellersarerotatingwithoutdissonance. 1
Checkthatantivibrationmountsareintact. 1
Checkthattheunitisoperationwithoutvibrationsafterthe
cleaning,overhaulandmaintenance.
1
Rotaryheat
exchanger
Checkthatleakageanddirtaccumulationisinsignificant 1
Checkthattherotorcanturnfreelyandeasilymanuallywitha
handwhenthebeltisremovedfromthedrive
1
Plateheat
exchanger
Checkbypassfunctionandsequencefordeicing 1
Runaroundheat
exchanger
Checktheexchanger functionandtestthefrostprotection.The
glycolmustbewithoutadditivesandautoglycolmustnotbe
used.
Dampers Testtheoperation. 1
Visualinspectionofsealsandtightnesswhenclosed. 1
Hotwaterbattery
Checkthedirtaccumulationandclean,ifneeded. 1
Bleeding,ifneeded. 1
Testoffrostprotectionsequence 1
Testofcirkulationpump 1
Electricheating
battery
Checkdirtaccumulationandclean,ifneeded. 1
Testthefunctionofthesystemwiththefusesforthesafety. 1
Coolingbattery Checkdirtaccumulationandclean,ifneeded. 1
Testthefrostprotection(glycol) 1
Coolingcompressor
unit
Mandatoryannualcontrolofthecompressorsystem.Mustbe
donebycertifiedtechnicianfromacertifiedcompany.
1
Condensatedrain Cleaningoftray,watertrapandoutlet.Checktheelectrical
heatingbetweeninsulationandpipes,ifinstalled.
1
Saving‐andcomfort
functions
TestofCO2sensor,humiditysensor,motionsensor,pressure
transmittersforaircapacitycontrol,extendedoperationvia
button,coolingrecovery,freecooling
1
Firealarm Testofthermostats,smokedetectorsandfiredetection
systems
1
Batteryincontroller Changethebatteryondemandbyalarminthedisplayand
alwayschangethebatteryasaminimumevery5.Year.
1
Remotecontrol TestofCommunications. 1

Table of Contents

Other manuals for SystemAir Danvent DV