39
ThecontrollerhasbeenpreparedwithaWEBmasterinterface(WEBsideintegrated)availablewhen
connectedtoaLANnetwork.ItispossibleviatheLANnetworktoreadvaluesandtochangesome
parametersforexamplesetpointtemperatures,schedules,airflowcapacity.Itispossibletoreadand
resetpresentalarms.Thereare2levelsoflogin.
k.6.1.2CommunicationtoBMSsystemswithMODBUS
Thecontrollerhasbeenpreparedforcommu nicationviaRS485communicationporttoaMODBUSbased
BMSsystem(BuildingManagementSystem).
Thecontrollercanworkasastandalonesystemwithoutanysupportfromother
controllers.Specialsetup
ofthecontrollerforcommunicationwiththeBMSsystemisnotincludedinthedeliveryfromSystemair.
k.6.1.3CommunicationtoBMSsystemswithLON
Thecontrollerhasbeenpreparedforcommu nicationviaLONcommunicationporttoBMSsystems
(BuildingManagementSystems).TheportusesLonWorksaccordingtotheLonMark
guidelines.TheLON
interfacevariablesareavailablefromSystemair.Thecontrollercanworkasastandalonesystemwithout
anysupportfromothercontrollers.Specialsetupofthecontrollerforcommuni cationwiththeBMS
systemisnotincludedinthedeliveryfromSystemair.
k.6.1.4CommunicationtoBMSsystemsvia
BACnet
ThecontrollerhasbeenpreparedforBACnetTCP/IPinterface.Thiscanbeusedforcommunicationwitha
BMSsystem(BuildingManagementSystem).
Thecontrollercanworkasastandalonesystemwithoutanysupportfromothercontrollers.Specialsetup
ofthecontrollerforcommunicationwiththeBMSsystemis
notincludedinthedeliveryfromSystemair.
K.6.2Extendedoperationandexternalstart/stop(forexamplebypresencedetectors)
Whentheunitisrunningatreducedspeedorisinshutdownmode,itcanbeforceduponestepbyusinga
Pushbutton(impulse).Therequirednumberofminutesfortheextendedoperationmustbeselectedon
theSystemairControlPanel.ButtonandcablearenotdeliveredbySystemair.
Furthermorewhentheunitis
inshutdownmodeitispossibletostart/stoptheunitbypresencedetectors.Presencedetectorsandcable
arenotdeliveredbySystemair.
k.6.3Valveandvalvemotorforheatingcoil
Thesupplyvoltageforthewatervalveactuatoris24VAC,thecontrolsignalis010V.Thesensorforwater
temperaturehastobeinstalledintheheatingcoilandthesensorisprovidedwithcablebutnotconnected
totheterminalsinthecabinet.Thecablebetweenvalve
motorandterminalsinthecabinetisnotdelivered
bySystemair.Standardvalvesareavailablefor2or3wayconnection.
k.6.4Valveandvalvemotorforcoolingcoil
Thesupplyvoltageforthewatervalveactuatoris24VAC,thecontrolsignalis010V.Cablesbetweenvalve
motorandterminalsinthecabinetarenotdeliveredbySystemair.Standardvalvesareavailablefor2or3
wayconnection.
k.6.5DXcooling
ADXcoolercanbeconnectedtothecontroller.Inputandoutputareavailablefor:
StartcoolingAlarmcoolingCoolingY3.CablesarenotdeliveredbySystemair
k.6.6Circulationpump,heating
CirculationpumpisnotincludedinthedeliveryfromSystemair.Ifthepumphasnotbeenactivatedfor24
hours,thepumpisexercisedoncedailyfor1minutetokeepthepumpinagoodcondition.Cablesarenot
deliveredbySystemair.