EasyManua.ls Logo

SystemAir Danvent TIME - Unintended Use And Misuse - Inappropriate Applications For The Machine; ; H.1 Air Handling Unit in Operation; Employees In Charge Of Operation;Control;Maintenance

SystemAir Danvent TIME
60 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
23
Operator’sGuideannex17
Instructionsforuseofthemachinesectionkinthismanual
Instructionsaboutadjustmentandmaintenancesectionrinthismanual
Safetyduringadjustmentandmaintenancesections
f.Employeesinchargeofoperation/control/maintenance
Theunitisabletooperatefullyautomaticallywhentheinstaller hasstarted,adjustedandhandedoverthe
faultlessunittothestaffthattakescareofoperation,controlandmaintenance.
f1.Employeesthattakecareofordinaryoperation
IndicationsofoperationstatusaswellasindicationoffaultsarevisibleinthedisplayandontheLED’sof
thehandterminal.Theemployeescanenternewparametersinthecontroller viathebuttonsonthehand
terminal.ThealternativeisthatthecontrollerisconnectedtoaBMSsystem
withtheabilitytoselectnew
parametersviaPC,tablet,SmartPhoneormobilephone.
g.Intendeduseandrangeofapplications
Theairhandlingunitsareintendedforthetransportandtreatmentofairbetween‐40°Cand+40°C
Theunitsareexclusivelyforcomfortventilationandnotforairthatcausesseverecorrosiontogalvanized
steelandtocopperandaluminum.Theunitsarenotforenvironmentsthatexceed
thecorrosionclassC4
accordingtoENISO129442.
Intendedapplicationsfortheunitsare:
Offices,teachingrooms,hotels,shops,homesandsimilarcomfortzones.
h.Unintendeduseandmisuseinappropriateapplicationsforthe
machine
TheairhandlingunitsarenotsuitablefortransportofairwithriskofexplosionandwithExClassification.
DonotinstalltheunitsinExareasatall.
Donotinstallunitsoutdoorsunlesstheunitsare constructedforoutdoorinstallation.Unitsnotsuitablefor
outdoorinstallationareunitswithout
roofandunitswithcabinetinstalledontheunit(thecabinetis
installedinsidetheunitforoutdoorinstallation).
TheunitsarenotforenvironmentsthatexceedthecorrosionclassC4accordingtoENISO129442,andthe
unitsarenotfortransportofsolidparticles.
Notintendedapplications
fortheunitsare:
Kitchenextraction,swimmingpools,offshore,Exareas,dryingofwashedclothes.
Donotusetheunitwithpartlyfinishedductsystems.Donotusetheunitforventilationofthebuildingsite
untiltheunitisproperlyprovidedwithguards.
h.1Airhandlingunitinoperation
Thepressuredifferencebetweeninteriorandexterioroftheunitmustnotexceed2000PafortheDV10
anduptoDV150(includingDV150),and1500PaforDV190andDV240.
Beforestartupoftheunitallducts,guardsandallprotectivedevicesmustbe
mountedtopreventany
accesstorotatingfanimpellers.Allinspectiondoorsmustbeclosedandlockedwhentheunitisin
operation.
Donotusetheunitwithoutfilters.

Table of Contents

Other manuals for SystemAir Danvent TIME

Related product manuals