SystemAir Danvent TIME - I.3.3.2 Necessary Mains Power Supply for DV Units with Cabinet;Control System; I.3.3.3 Necessary Overvoltage Protection Device, that Leads Lightning Overvoltage to an Earth Lead on a Safe Way; I.3.4 Electrical Connection of Components and Functions; I.3.4.1 Connection of the Systemair Control Panel to the Corrigo E28 Controller - Software Version 3.3

SystemAir Danvent TIME
60 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
32
Unit Motor Fuse
Minimum
Fuse
Maximum
Maximum
Shortcircuitcurrent
TIME10 2*0.94kW
2*0.99kW
10A 16A 16kA
TIME15 2*0.99kW
2*1.7kW
10A
13A
25A 16kA
TIME20 2*1.7kW
2*3.0kW
13A 25A 16kA
TIME25 2*3.0kW
2*2.73kW
13A
13A
25A 16kA
TIME30 2*2.73kW
2*5.18kW
20A 32A 16kA
TIME40 2*5.18kW
2*4.7kW
20A
20A
32A 16kA
i.3.3.2NecessarymainspowersupplyforDVunitswithcabinet/controlsystem
Necessarymainspowersupplyisprintedontheuniquemachinecardplacedonthefrontofeveryunit(see
exampleofamachinecardinsectiond.2.1).
i.3.3.3Necessaryovervoltageprotectiondevice,thatleadslightningovervoltagetoanearthlead
ona
safeway.
TheInstallerandusermustbeawareofthefactthatlightningstrikesmakeariskthatrequiresinstallation
ofovervoltageprotectiondevicestoleadtheli ghtningovervoltagetoanearthleadinasafeway.
Installerandusermusttakecareofthisaccordingto
localstatutoryrequirements.
i.3.4Electricalconnectionofcomponentsandfunctions
Externalcomponentsandfunctionsaredeliveredaccordingtotheorderconfirmation.Cablenumber’sare
writtenonthecables,onthelabelwithterminalplanonorwiththecabinetseesectiond.2.5andinthe
wiringdiagramsannex16.
i.3.4.1ConnectionoftheSystemairControlPaneltotheCorrigo
E28controllersoftwareversion3.3
TheSCPpanelpartnumberS208997forsoftwareversion3.3‐isprovidedwith10metresofcableanda
socketforconnectionwiththecontrollerinsidethecabinet.Thecableisnotpulledthroughthecableentry
inthecabinet,sodemount
thecableatthebackoftheSyste mairControlPanel‐pullthecablethroughthe
cableentryinthecabinet‐adjustthelengthofthecableandremountthecableinthepanel,oraddmore
cableupto100mofcablebetweentheSystemairControlPanelandthe
controllerispossible.Placethe
SystemairControlPanelontheoutersideoftheunitoronawall.