EasyManua.ls Logo

SystemAir Danvent TIME - K.6.1.2 Communication to BMS Systems with MODBUS; K.6.1.3 Communication to BMS Systems with LON; K.6.1.4 Communication to BMS Systems Via Bacnet; K.6.2 Extended Operation and External Start;Stop (for Example by Presence Detectors)

SystemAir Danvent TIME
60 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
39
ThecontrollerhasbeenpreparedwithaWEBmasterinterface(WEBsideintegrated)availablewhen
connectedtoaLANnetwork.ItispossibleviatheLANnetworktoreadvaluesandtochangesome
parametersforexamplesetpointtemperatures,schedules,airflowcapacity.Itispossibletoreadand
resetpresentalarms.Thereare2levelsoflogin.
k.6.1.2CommunicationtoBMSsystemswithMODBUS
Thecontrollerhasbeenpreparedforcommu nicationviaRS485communicationporttoaMODBUSbased
BMSsystem(BuildingManagementSystem).
Thecontrollercanworkasastandalonesystemwithoutanysupportfromother
controllers.Specialsetup
ofthecontrollerforcommunicationwiththeBMSsystemisnotincludedinthedeliveryfromSystemair.
k.6.1.3CommunicationtoBMSsystemswithLON
Thecontrollerhasbeenpreparedforcommu nicationviaLONcommunicationporttoBMSsystems
(BuildingManagementSystems).TheportusesLonWorksaccordingtotheLonMark
guidelines.TheLON
interfacevariablesareavailablefromSystemair.Thecontrollercanworkasastandalonesystemwithout
anysupportfromothercontrollers.Specialsetupofthecontrollerforcommuni cationwiththeBMS
systemisnotincludedinthedeliveryfromSystemair.
k.6.1.4CommunicationtoBMSsystemsvia
BACnet
ThecontrollerhasbeenpreparedforBACnetTCP/IPinterface.Thiscanbeusedforcommunicationwitha
BMSsystem(BuildingManagementSystem).
Thecontrollercanworkasastandalonesystemwithoutanysupportfromothercontrollers.Specialsetup
ofthecontrollerforcommunicationwiththeBMSsystemis
notincludedinthedeliveryfromSystemair.
K.6.2Extendedoperationandexternalstart/stop(forexamplebypresencedetectors)
Whentheunitisrunningatreducedspeedorisinshutdownmode,itcanbeforceduponestepbyusinga
Pushbutton(impulse).Therequirednumberofminutesfortheextendedoperationmustbeselectedon
theSystemairControlPanel.ButtonandcablearenotdeliveredbySystemair.
Furthermorewhentheunitis
inshutdownmodeitispossibletostart/stoptheunitbypresencedetectors.Presencedetectorsandcable
arenotdeliveredbySystemair.
k.6.3Valveandvalvemotorforheatingcoil
Thesupplyvoltageforthewatervalveactuatoris24VAC,thecontrolsignalis010V.Thesensorforwater
temperaturehastobeinstalledintheheatingcoilandthesensorisprovidedwithcablebutnotconnected
totheterminalsinthecabinet.Thecablebetweenvalve
motorandterminalsinthecabinetisnotdelivered
bySystemair.Standardvalvesareavailablefor2or3wayconnection.
k.6.4Valveandvalvemotorforcoolingcoil
Thesupplyvoltageforthewatervalveactuatoris24VAC,thecontrolsignalis010V.Cablesbetweenvalve
motorandterminalsinthecabinetarenotdeliveredbySystemair.Standardvalvesareavailablefor2or3
wayconnection.
k.6.5DXcooling
ADXcoolercanbeconnectedtothecontroller.Inputandoutputareavailablefor:
StartcoolingAlarmcoolingCoolingY3.CablesarenotdeliveredbySystemair
k.6.6Circulationpump,heating
CirculationpumpisnotincludedinthedeliveryfromSystemair.Ifthepumphasnotbeenactivatedfor24
hours,thepumpisexercisedoncedailyfor1minutetokeepthepumpinagoodcondition.Cablesarenot
deliveredbySystemair.

Table of Contents

Other manuals for SystemAir Danvent TIME

Related product manuals