EasyManua.ls Logo

SystemAir Danvent TIME - L.8 Batteries for Heating and Cooling Type DVR - DVH - DVK, Cooling Compressor; L.8.1 Extreme Temperatures - Heating; L.8.2 Extreme Temperatures - Cooling; L.9 Cooling Compressor Units Type DVU - DVU-C

SystemAir Danvent TIME
60 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
46
l.8BatteriesforheatingandcoolingtypeDVRDVHDVK,coolingcompressor
l.8.1Extremetemperatures‐heating
Hazards/dangerousarea:
Electricalheatingelementscanachievesurfacetemperatureof500degreeCelsius.
Batteriesandpipesforhotwatercanachieve95degreeCelsius.
Dangerousincident:
AccordingtoISO137321:2006,hereisnodirectriskofburns.(shorttimecontactlesserthan2,5sec).
Claimforreductionofdanger:
No.
l.8.2Extremetemperatures‐cooling
Hazards/dangerousarea:
Evaporatorbatteriesandpipesconnectedtocoolingcompressorcanachieveminus10degreesCelsius.
Dangerousincident:
AccordingtoISO137321:2006,hereisnodirectriskofburns.(shorttimecontactlesserthan2,5sec).
Claimforreductionofdanger:
No.
l.9CoolingcompressorunitstypeDVUDVUC
l.9.1Riskofhightemperature
Hazards/dangerousarea:
Condenserbatteriesandpipescanachievetemperatureof60degreeCelsius.
Dangerousincident:
VurderetudfraISO137321:2006,dererumiddelbartikkerisikoforforbrændinger.(berøringstid2,5sek).
Claimforreductionofdanger:
No.
l.9.2Riskcausedbylightningstrike
Hazards/dangerousarea:
Lightningstrikeclosetothemachine.
Dangerousincident:
Lightningstrikecancreateflashoverbetweenphasesandconductiveparts.Thiscancausefireorthe
overvoltagecanmakeinjuryonpersons
Claimforreductionofdanger:
Installerandusermustbeawareofthefactthatlightningmakesariskthatrequiresinstallationof
overvoltageprotectiondevicestoleadthelightningovervoltagetoanearthleadonasafeway.Theneed
forovervoltageprotectiondevicesdependonwheretheunitis placedinandonthe
building.
Installerandusermusttakecareofthisaccordingtolocalstatutoryrequirements.Overvoltageprotection
devicesarealsodescribedinsectioni.3.3.3ofthismanual
m.Instructionsontheprotectivemeasurestobetakenbyallservice
techniciansduringrepairandmaintenance
Usethebelowmentionedpersonalprotectiveequipmentformaintenance:
Cutresistantglovesforprotectionagainstinjuryfromsharpmetalplateedges.UseCEmarked
glovesforthispurpose.

Table of Contents

Other manuals for SystemAir Danvent TIME

Related product manuals