30
i.2.8Fittingtheductwork
FlexibleductconnectionsbetweenAHUandductworkmustalwaysbeinstalled.Besurethatflexibleduct
connectionsarealmostfullystretched.(Flexibleconnectionsareorderedasaccessoriesandtheyareplaced
insidetheunit).Atthefanoutletonacentrifugalfan,theductsizeshouldbeascloseto
theoutletsizeas
possible.Avoidblockageandturbulenceatthefanoutlet.
i.2.9Riskofstackeffectbyverticalductsandwindpressureonlouvers
Onspecialoccasionsstackeffectalsocalledchimneyeffectintheductscreateairflowsthatdrivesthe
impellersbyturnedoffmotors.
Arotatingimpellerisapotentialhazardduringcleaningandmaintenanceoftheunit.
Eliminatethisairflowbydamperswithspringreturnmotorsforautomaticclosingof
thedampers‐evenby
powerfailure.
Important!TheSystemairairhandlingunitscanbeorderedanddeliveredwithoutdampers,andthe
installer/usermustcheckthatductsystemswiththedescribedriskofstackeffect(chimneyeffect)willbe
providedwithdampersandspringreturnmotors.
i.2.10Refittingofguards
Theguardisasafetyguardinstalledinsidethedoor.Toolsarenecessaryfortheremovaloftheguard.Ifthe
guardhasbeendemountedduringtheinstallationonthesite,theguardmustberefittedbeforestartupof
theunit.