EasyManua.ls Logo

SystemAir Danvent TIME - I.1.8 Pre-Assembly Storage; I.1.9 Tilt Less than 30˚ During Transportation of the Section with Cooling Compressor - DVU or DVU-C; I.2. Installation - Mechanical; I.2.1 Free Area in Front of and above the Unit

SystemAir Danvent TIME
60 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
26
i.1.8Preassemblystorage
TheAHUmustbeprotectedfromtheweatherandaccidentalimpact.Plasticpackagingmustberemoved
andtheunitcoveredwithtarpaulinorsimilarmaterials.Inordertominimizecondensation,sufficientair
circulationmustbeensuredbetwee nthecoveringandtheunit.
i.1.9Tiltlessthan30˚duringtransportationofthesectionwithcoolingcompressor
DVUorDVUC
Duringtransportation,theunitsection ‐DVUorDVUC‐mustalwaysbeintheuprightpositionortiltedless
than30˚.Ifitisnecessarytotilttheunitmorethan30˚,thesuctionpipeofthecompressormustpoint
upwardstopreventtheescapeofoilfr omthecompressorsump.
i.2.Installation‐mechanical
i.2.1Freeareainfrontofandabovetheunit
Important!Whenpositioningtheunitonthesite,itmustbeensuredthatanareawiththesamewidthas
theunitiskeptfreeforserviceandinspectionandalsoforreplacementoffansandexchanger,ifneeded.
Thewidthofthefreeareamustbeatleast900mm.
Important!Forsafeaccesstothecabinetwithelectricalcomponents,ifthecabinetisplacedontopofthe
unit,thefreeareafromtheupperedgeofthecabinettotheceilingmustbeatleast700mm.
i.2.2Supportingsurface
Thesurfacebeneaththeunitmustbelevel,horizontalandvibrationfree.Thesurfacemustbeableto
withstandtheloadoftheAHU.WeightsofthesectionsarewritteninAnnex2.
Remember!Ductworkmustbesoundinsulatedandmustnotbemounteddirectlyonbeams,trussesor
other
criticalbuildingparts.
i.2.3Adjustablefeetunderlegsorbaseframeandtransportofsections
Adjustablefeetareprovidedinacartonboxplacedinsidetheunit.Adjustablefeetaredeliveredforindoor
unitsandnotforoutdoorunits.
Sectionscanbetransportedonthesitebyhandmanualforkliftsorsimilar.Theframeprofilesintheedges
ofthesectionshavecarryingcapacity
forliftingbythehandmanualforklifts.
i.2.4Baseframeassembly
Thebaseframeisdeliveredunassembledandhastobeassembledonthesitebeforeitispossibleto
positionandassemblethevarioussectionsoftheAHU.Assemblyofthebaseframeisillustratedon4pages
inamanualthatisalwaysinaplasticfolderandis attached
tooneofthelargebaseframeparts.This
manualisavailableonthesiteamongthebaseframeparts.
Therearetwotypesofbaseframes:
1.
150mmhighbaseframes
2.
250mmhighbaseframes