3. Sectionsaremountedtobaseframeswithlongselfdrillingscrews.Theframeprofileunderthe
inspectiondoorsisplacedoverthehorizontalprofileofthebaseframe.Seetheexampleonthe
photobelow.
i.2.7JoiningtheAHUsections
Thesectionsmustbeplacedonthebaseframeandiftheunitisdeliveredwith100mmlegs, thesections
mustbepositioneddirectlyoppositeeachother.
1.
Ensurethattheinternalfactoryfittedrubbersealingisundamaged
2.
Thesectionsarethentobepositioneddirectlyoppositeeachother.Ifthesectionsarebuiltwith
legs,theadjustablefeetcanbeusedtogetthesectionsparallelandatthesameheight.
3.
Pressthesections
hardtogethersothattherubberprofilesaresoflatthattheironframesofthe
twosectionsarejoined.Strapswithtensionerasshownbelowaresuitableforpressingthesections
hardtogether.
4.
ThesectionsarethentobelockedpermanentlytogetherwiththeblackplasticcoatedSystemair
DiscLocks.TheDiscLocksaredeliveredinacartonboxplacedinsidetheunit.PlaceeachDiscLock
overthe2factoryfittedlockingpins.Thediscsandlockingpinsarenotreliableforpullingthe
sectionstogether.Theyareonlysufficientforkeepingthesectionswelltogether,sojust
turneach
discgentlywiththesuppliedAllenkey.Useasequencewhereeachdiscistightenedwithonlyone
clickatatime.Iftheunitisplacedtooclosetoawallwithnospaceleftforthemountingof
SystemairDiscLocks,bracketsmustbeplacedinside
theunittokeepthesectionspermanently
together(bracketsforthispurposearenotdeliveredbySystemair)