38
k.3Documentationisavailablefordownloadfromhttps://techdoc.systemair.dk
YourlocalSystemaircompanyisabletoprovidethedataorpossiblyaPassword.
k.4Startupbyinstaller
Allprotectionandsafetymeasuresmustbemetbeforestartupoftheunit.Themainssupplyvoltagemust
alsobecheckedtoo.Themainssupplyvoltagemustbemeasuredatthesupplyterminalsinthecabinet.
k.4.1Checklist,relevantvalues
k.4.1.1Checklistpriortostartup
Istheunitassembledcorrectlywithitsfunctionsinthecorrectorder?Seeannex2.
Arethesectionsandductsassembledcorrect?Seeannexi.
Checkthatfansandantivibrationmountsarenotdamagedaftertransportationandinstallation.
Isthe
rotaryexchangerturningfreely?
Aresafetyguardsinstalledcorrectly?
Iftheunitincludesintegratedcooling(DVU),checkwhetheritisinstalledandsupervisedby
qualifiedservicepersonnel.
IftheunitcontainsElectricairheater,makesurethatthesupplyisolatordisconnectswiththeunit.
Ducts‐are
allductsinstalled?
Externalcomponents‐arethevalveandvalvemotorinstalledcorrectly?
Isthecirculationpumpinstalledcorrectly?
Iswaterunderpressureinthecoilandcirculationpump?
Arethepressuretransmittersinstalledandconnectedcorrectly?(Ifthisisasystemwithpressure
transmittersin
theducts)
Mainpowersupply:
o Connectedcorrectly?(3x400V+N+PE)
o Testofsupplyvoltageforactuatorsandcontrolsignal!
o Arecontrolsignalsforactuatorsconnectedcorrectly?
k.4.1.2Switchonpower
Donotstartuntilallsafetyprocedureshavebeencompletedandensurethatinspection
doorsareclosed
andlocked.
Switchonpowerandtheunitshouldbereadyforthestartup.
ForstartupseetheOperator’sguidefortheSystemaircontrolpanel‐annex 17(thismanualisdelivered
withtheunitprintedonpaperand alsoavailableonthedeliveredDVD).
K.5Adjustmentsanduse
AdjustthefactorysetvaluesforparametersontheSystemairControlPanelorviathesoftwareEToolona
PC.SeetheOperator’sguidefortheSystemaircontrolpanel‐annex17(thismanualisdeliveredwiththe
unitprintedonpaperandalsoavailableonthedeliveredDVD.Further
informationaboutthecontrolleris
availableonthe100pagesintheCorrigoE28UserManualthatisavailableonthedeliveredDVD.
EToolsoftwareisalsoavailableonthedeliveredDVDandfordownloadfromahomepage.
K.6Descriptionoffunctions
K.6.1Remotecontrol
k.6.1.1CommunicationWEBmaster(TCP/IPExoline)toPCandAndroidtelephone

Table of Contents