EasyManua.ls Logo

SystemAir Danvent TIME - K.6.10 Speed Control of Fans; K.6.10.1 TIME Control System - EC Motors; K.6.10.2 DV Control System - Frequency Converters Inside the Unit Are IP 20; K.6.10.3 Pressure Transmitters

SystemAir Danvent TIME
60 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
41
k.6.10Speedcontroloffans
k.6.10.1TIMEcontrolsystemECmotors
FanmotorrevolutionsarecontrolledbytheECmotors.TheECmotorsareconfiguredandtestedtocomply
withthedataoftheunit.
k.6.10.2DVcontrolsystem‐frequencyconvertersinsidetheunitareIP20
Fanmotorrevolutionsarecontrolledbyfrequencyconverters,
andtheyareconfiguredandtestedto
complywiththedatafortheunit.Thefrequencyconverterforeachfanmotorisinstalledinsidetheunit
besidethefanmotorwithcablesbetweenmotorandconverter.Inunitswithcompletecontrolsystemthe
frequencyconvertersaredeliveredwithsystemparameters
adaptedtothemotorsandtheproject.
k.6.10.3Pressuretransmitters
Separatecontroloftheairfloworductpressureforsupplyfanandforextractfan.Therequiredairflowor
ductpressureswithnormalaswellasreducedcapacityareselectedontheSystemairControlPanel.
Theactualpressureis
measuredbypressuretransmitters.PIcalcul ationinthecontrollercontinuously
transmitsthenecessaryrevolutionsforthefanstothefrequencyconverterstoachievetherequired
pressure.
k.6.10.4CO2dependentairflow
TheairflowiscontrolledbyaCO
2
sensor.HighCO
2
concentrationisequaltohigherairflow.LowCO
2
concentrationisequaltolowerairflow.BasedontheactualCO
2
levelandamin/maxlevel,theneeded
airflowiscalculated.Thespeedofeachfanisadjustedviafrequencyconverter.Terminalsinthecabinetare
availableforconnectionofthesensor.
k.6.10.5Humiditydependentairflow
Theairflowiscontrolledbythehumiditysensor.Highhumidityisequalto
higherairflow.Lowhumidityis
equaltolowerairflow.Basedontheactualhumiditylevelandamin/maxleveltheneededairflowis
calculated.Thespeedofeachfanisadjustedviafrequencyconverter.Terminalsinthecabinetareavailable
forconnectionofthesensor.
k.6.11Cabinet
k.6.11.1IntegratedcabinetsinTIMEunits
TIMEunitsaredeliveredwith2integratedcabinets.Onecabinetinthesupplyfansectionandonecabinet
inexhaustfansection.Bothcabinetsareinstalledbehindinspectiondoors.Externalcomponentsmustbe
connectedtoterminalsinthecabinetinthesupplyfansection.
k.6.11.2
IntegratedcabinetinDVunitswithcontrolsystem
Cabinetisintegratedintheunitbehindaninspectiondoor.Terminalsareinstalledinthecabinetforall
externalcomponents.Thenumberofterminalsisalwaysadaptedtotheindividualorder.
k.6.11.3CabinetplacedontheDVunitwithcontrolsystem
The
modelswiththecabinetontheunitareexclusivelyforindoorinstallation.Terminalsareinstalledinthe
cabinetforallexternalcomponents.Thenumberofterminalsisalwaysadaptedtotheindi vidualorder.
k.6.12Temperaturesensors
Foursensorsarealwaysdeliveredwitheachunit.Seebelowwherethesensorsareplaced;
1sensorintheextractair,installedinsidetheunit

Table of Contents

Other manuals for SystemAir Danvent TIME

Related product manuals