Group 07: Start /Stop Parameters
Code
Parameter
Name
Setting Range Default
Attrib
ute
07-07
DC Injection
Braking
Current
0~100 50
07-08
DC Injection
Braking Time
at Stop
0.00~100.00 0.50
07-09
Stop Mode
Selection
0: Deceleration
to Stop
0
1: Coast to Stop
2: DC Braking
Stop in All
Fields
3: Coast to Stop
with Timer
07-10
~
07-12
Reserved
07-13
Low Voltage
Detection
Level
200V: 150~300 190
400V: 250~600 380
575V: 500~600 546
690V: 500~600 546
07-14
Pre-excitation
Time
0.00~10.00 2.00
07-15
Pre-excitation
Level
50~200 100
07-16
DC Injection
Braking Time
at Start
0.00~100.00 0.00
07-17 Reserved
07-18
Minimum
Base block
Time
0.1~5.0 -
07-19
Direction-
Detection
Speed
Search
Operating
Current
0~100 50
07-20
Speed
Search
Operating
Current
0~100 20
07-21
Integral Time
of Speed
Searching
0.1~10.0 2.0
07-22
Delay Time of
Speed
Searching
0.0~20.0 0.2
07-23
Voltage
Recovery
Time
0.1~5.0 2.0
07-24
Direction-
Detection
Speed
Search
Selection
0: Disable
1
1: Enable
07-25
Low Voltage
Detection
Time
0.00~1.00 0.02
Group 07: Start /Stop Parameters
Code
Parameter
Name
Setting Range Default
Attrib
ute
07-26
Start-up Mode
Selection of
SLV Coast to
Stop
0: Start with
speed search
0
1: Normal start
07-27
Start Selection
after Fault
during SLV
Mode
0: Start with
speed search
0
1: Normal start
07-28
Start after
External Base
Block
0: Start with
speed
search
0
1: Normal start
07-29
Run
Command
Selection at
the Action of
DC Braking
0: Not Allowable
to Run
0
1: Allowable to
Run
07-30
Low Voltage
Level
Selection
0: Disable
0
1: Enable
07-31
**Low Voltage
Run
Frequency
0.00~599.00 10.00
07-32
Speed
Search Mode
Selection
0: Disable
0
1: Mode1:
Execute a
Speed Search at
Power On
2: Execute a
Speed Search
each time
07-33
Start
Frequency of
Speed
Search
Selection
0: Maximum
Output
Frequency of
Motor
0
1: Frequency
Command
07-34
Start short-
circuit braking
time
0.00~100.00 0.00 Note1
07-35
Stop Short-
circuit braking
time
0.00~100.00 0.50 Note1
07-36
Short-circuit
braking
current limited
0.0~200.0 100.0 Note1
07-37
~
07-41
Reserved
07-42
Voltage Limit
Gain
0.0~50.0 0 Note2
07-43
Short-circuit
Braking Time
of PM Speed
Search
0.00~100.00 0.00 Note3
07-44
DC Braking
Time of PM
Speed
Search
0.00~100.00 0.00 Note3
07-45 STP2 0: STP2 Enable 0 Note4