24
Group 07: Start /Stop Parameters
Code
Parameter
Name
Setting Range Default
Attrib
ute
Function
Selection
1: STP2 Disable
07-46
DC Injection
Current Limit
0~150 100 Note5
*07-13 Low Voltage Detection Level, it is enable when
07-30 Low Voltage Level Selection set 0 (Enable) and
lower frequency limit set to 250V.This application is
for Emergency power supply (EPS)
* *If the maximum output frequency of motor is over
300HZ, the frequency resolution is changed to 0.1Hz
Group 08: Protection Parameters
Code
Parameter
Name
Setting Range Default
Attrib
ute
08-00
Stall
Prevention
Function
xxx0b: Stall
prevention is
enabled in
acceleration.
0000b
xxx1b: Stall
prevention is
disabled in
acceleration.
xx0xb: Stall
prevention is
enabled in
deceleration.
xx1xb: Stall
prevention is
disabled in
deceleration.
x0xxb: Stall
prevention is
enabled in
operation
x1xxb: Stall
prevention is
disabled in
operation
0xxxb: Stall
prevention in
operation is based
on deceleration
time of speed-
stage 1.
1xxxb: Stall
prevention in
operation is based
on deceleration
time of speed-
stage 2.
08-01
Stall
Prevention
Level in
Acceleration
20~200
HD:150
ND:120
08-02
Stall
Prevention
200V: 330V~410V
385V
400V: 660V~820V
770V
Group 08: Protection Parameters
Code
Parameter
Name
Setting Range Default
Attrib
ute
Level in
Deceleration
575V:900~1000
950V
690V:1080~1200
1140V
08-03
Stall
Prevention
Level in
Operation
30~200
HD:160
ND:120
08-04 Reserved
08-05
Selection for
Motor
Overload
Protection
(OL1)
xxx0b: Overload
Protection is
disabled.
0001b
xxx1b: Overload
Protection is
enabled.
xx0xb: Cold Start
of Motor
Overload
xx1xb: Hot Start
of Motor
Overload
x0xxb: Standard
Motor
x1xxb: Inverter
Duty Motor
0xxxb: Reserved
1xxxb: Reserved
08-06
Start-up
Mode of
Overload
Protection
Operation
(OL1)
0: Stop Output
after Overload
Protection
0
1: Continuous
Operation after
Overload
Protection.
08-07
Motor
Overload
(OL1)
Protection
Level
0: Motor
Overload (OL1)
Protection 0
0 Note2
1: Motor
Overload (OL1)
Protection 1
2: Motor
Overload (OL1)
Protection 2
08-08
Automatic
Voltage
Regulation
(AVR)
0: Enable
0
1: Disable
08-09
Selection of
Input Phase
Loss
Protection
0: Disable
0
1: Enable
08-10
Selection of
Output Phase
Loss
Protection
0: Disable
0
1: Enable
08-11
08-12
Reserved
08-13
Selection of
Over-Torque
Detection
0: Over-Torque
Detection is
Disabled.
0
1: Start to Detect