Group 08: Protection Parameters
Code
Parameter
Name
Setting Range Default
Attrib
ute
Stall
Prevention
Limit
08-42
PTC
Protection
Level
0.1~10.0V 0.7
08-43
PTC Restart
Level
0.1~10.0V 0.3
08-44
PTC Warning
Level
0.1~10.0V 0.5
08-45 Reserved
08-46
Over-
temperature
Protection
Level
0~254°C 0 Note6
08-47
Over-
temperature
Reset Level
0~254°C 0 Note6
08-48
Fire Mode
Selection
0: Disable
1: Enable
0 Note6
08-49
Fire Mode
Digital Input
Type
0: Power Loss
Reset
1: Terminal
Removal
Resset
0 Note6
08-50
Fire Mode
Digital
Terminal
Status
XXX0b: S6 A
contact
XXX1b: S6 B
contact
0000b Note6
08-51
Fire Mode
Motor Speed
Selection
0: Fire Mode
Operation
1: PID
Frequency
Command
2: AI2 Frequency
Command
0 Note6
08-52
Fire Mode
Motor Speed
0.00~100.00 100.00 Note6
08-53
Fire Mode
PID Detection
Level
0~100 0 Note6
08-54
Fire Mode
PID
Disconnection
Delay
0.0~10.0 1.0 Note6
08-55
Fire Mode
PID
Disconnection
Selection
0: Current Speed
1: Fire Mode
Speed (08-52)
2: Motor 1
Maximum
Frequency (01-
02)
1 Note6
08-56
Fire Mode AI2
Detection
Level
0.0~100.0 80.0 Note6
08-57
Fire Mode AI2
Disconnection
Delay
0.0~10.0 1.0 Note6
08-58 Fire Mode AI2 0: Current Speed 1 Note6
Group 08: Protection Parameters
Code
Parameter
Name
Setting Range Default
Attrib
ute
Disconnection
Selection
1: Fire Mode
Speed (08-52)
2: Motor 1
Maximum
Frequency (01-
02)
08-59
Fire Mode
Motor
Direction
0: Forward
Direction
1: Reverse
Direction
0 Note6
08-60
Fire Mode
Password
00000~65534 0 Note6
Note: Models of 200V 50HP and 400V 100HP and above
don’t have this function.
Group 09: Communication Parameters
Code
Parameter
Name
Setting Range Default
Attrib
ute
09-00
INV
Communicati
on Station
Address
1~31 1 *3
09-01
Communicati
on Mode
Selection
0: MODBUS
0
*3
*5
1: Reserved
2: Reserved
3: Reserved
4: PROFIBUS*
09-02
Baud Rate
Setting (bps)
0: 1200
4 *3
1: 2400
2: 4800
3: 9600
4: 19200
5: 38400
09-03
Stop Bit
Selection
0: 1 Stop Bit
0 *3
1: 2 Stop Bit
09-04
Parity
Selection
0: No Parity
0 *3 1: Even Bit
2: Odd Bit
09-05
Communicati
on Data Bit
Selection
0: 8 Bit Data
0 *3
1: 7 Bit Data
09-06
Communicati
on Error
Detection
Time
0.0~25.5 0.0 *3
09-07
Fault Stop
Selection
0: Deceleration to
Stop Based on
Deceleration Time 1
when
Communication
Fault Occurs.
3 *3
1: Coast to Stop
when
Communication
Fault Occurs.