28
Group 10: PID Parameters
Code
Parameter
Name
Setting Range Default
Attrib
ute
10-28 Reserved
10-29
PID Sleep
Selection
0: Disable
1 1: Enable
2: set by DI
10-30
Upper Limit of
PID Target
0.0 ~ 100.0 100.0
10-31
Lower Limit of
PID Target
0.0 ~ 100.0 0.0
10-32 Reserved
10-33
Maximum
Value of PID
Feedback
1 ~ 10000 999
10-34
PID Decimal
Width
0 ~ 4 1
10-35 PID Unit
0: %
0 *7
1: FPM
2: CFM
3: SPI
4: GPH
5: GPM
6: IN
7: FT
8: /s
9: /m
10: /h
11: °F
12: inW
13: HP
14: m/s
15: MPM
16: CMM
17: W
18: KW
19: m
20: °C
21: RPM
22: Bar
23: Pa
24: KPa
10-36
Proportional
Gain 2 (P)
0.00~10.00 3.00 Note2
10-37
Integral Time
2 (I)
0.00~100.00 0.50 Note2
10-38
Differential
Time 2 (D)
0.00~10.00 0.00 Note2
10-39
*Output
Frequency
Setting of PID
Disconnection
00.00~599.00 30.00
10-40
Selection of
PID Sleep
Compensation
Frequency
0: Disable
0
1: Enable
10-41
PID Mode
Switch
0: General PID
0 Note2
1: D Type PID
10-42
~
Reserved
Group 10: PID Parameters
Code
Parameter
Name
Setting Range Default
Attrib
ute
10-46
10-47
Proportional
Gain 3(P)
0.00~10.00 3.00 Note4
10-48
Integral Time
3(I)
0.00~100.00 0.50 Note4
10-49
Differential
Time 3(D)
0.00~10.00 0.00 Note4
* If the maximum output frequency of motor is over
300HZ, the frequency resolution is changed to 0.1Hz
Group 11: Auxiliary Parameters
Code
Parameter
Name
Setting Range Default
Attrib
ute
11-00
Direction Lock
Selection
0: Allow
Forward and
Reverse
Rotation
0
1: Only Allow
Forward
Rotation
2: Only Allow
Reverse
Rotation
11-01
Carrier
frequency
0: Carrier
Output
Frequency
Tuning
1~16: 1~16KHz
* *1
11-02
Soft PWM
Function
Selection
0: Disable
0
1: Soft PWM 1
2: Soft PWM 2
11-03
Automatic
carrier lowering
selection
0: Disable
0
1: Enable
11-04
S-curve Time
Setting at the
Start of
Acceleration
0.00~2.50 0.20
11-05
S-curve Time
Setting at the
Stop of
Acceleration
0.00~2.50 0.20
11-06
S-curve Time
Setting at the
Start of
Deceleration
0.00~2.50 0.20
11-07
S-curve Time
Setting at the
Stop of
Deceleration
0.00~2.50 0.20
11-08
Jump
Frequency 1
0.0~599.0 0.0
11-09
Jump
Frequency 2
0.0~599.0 0.0
11-10 Jump 0.0~599.0 0.0

Other manuals for TECO A510s Series