29
Group 11: Auxiliary Parameters
Code
Parameter
Name
Setting Range Default
Attrib
ute
Frequency 3
11-11
Jump
Frequency
Width
0.0~25.5 1.0
11-12
Manual Energy
Saving Gain
0~100 80
11-13
Automatic
Return Time
0~120 60 *1
11-14
~
11-17
Reserved
11-18
Manual Energy
Saving
Frequency
0.0~599.0 0.00
11-19
Automatic
Energy Saving
Function
0: Automatic
energy saving
is disabled.
0
1: Automatic
energy saving
is enabled.
11-20
Filter Time of
Automatic
Energy Saving
0~200 140
11-21
Voltage Upper
Limit of Energy
Saving Tuning
0~100 100
11-22
Adjustment
Time of
Automatic
Energy Saving
0~5000 20 *1
11-23
Detection Level
of Automatic
Energy Saving
0~100 10
11-24
Coefficient of
Automatic
Energy Saving
0.00~655.34
(Note4)
-
11-25
~
11-27
Reserved
11-28
Frequency
Gain of Over
Voltage
Prevention 2
1~200 100
11-29
Auto De-rating
Selection
0: Disable
0
1: Enable
11-30
Variable Carrier
Frequency
Max. Limit
2~16 -
11-31
Variable Carrier
Frequency Min.
Limit
1~16 -
11-32
Variable Carrier
Frequency
Proportional
Gain
00~99 00
11-33
DC Voltage
Filter Rise
Amount
0.1~10.0 0.1 *1
11-34 DC Voltage 0.1~10.0 5.0 *1
Group 11: Auxiliary Parameters
Code
Parameter
Name
Setting Range Default
Attrib
ute
Filter Fall
Amount
11-35
DC Voltage
Filter Dead
band Level
0.0~99.0 10.0 *1
11-36
Frequency
Gain of OV
Prevention
0.000~1.000 0.050 *1
11-37
**Frequency
Limit of OV
Prevention
0.00~599.00 5.00
11-38
Deceleration
Start Voltage of
OV Prevention
200V: 200~400V
300
400V: 400~800V
700
575V: 500~1000V
900
690V: 600~1200V
1080
11-39
Deceleration
Stop Voltage of
OV Prevention
200V: 300~400V
350
400V: 600~800V
750
575V: 500~1000V
950
690V: 600~1200V
1140
11-40
OV Prevention
Selection
0: Disable
0
1: OV Prevention
Mode 1
2: OV Prevention
Mode 2
3: OV Prevention
Mode 3
11-41
Selection of
Reference
Frequency
Disappearance
Detection
0: Decelerate
to Stop when
Reference
Frequency
Disappears
0
1: Operation is
set by
Parameter 11-
42 when
Reference
Frequency
Disappears
11-42
Disappearance
Level of
Reference
Frequency
0.0~100.0 80.0
11-43
Hold
Frequency at
Start
0.0~599.0 0.0
11-44
Frequency
Hold Time at
Start
0.0~10.0 0.0
11-45
Hold
Frequency at
Stop
0.0~599.0 0.0
11-46
Frequency
Hold Time at
Stop
0.0~10.0 0.0
11-47
KEB
Deceleration
Time
0.0~25.5 0.0 *1
11-48
KEB Detection
Level
200V: 190~210 200
400V: 380~420 400