Chapter 6 FBD Block Diagram Programming 172
(2) Analog Comparison Mode 1~7
Analog comparator mode 1~7, setting three parameters, analog input Ax, analog input Ay and reference value G.
Analog Comparator mode 1: (Ay- reference value G)Ax(Ay+ reference value G) , output ON;
Analog Comparator mode 2: AxAy, output ON;
Analog Comparator mode 3: AxAy, output ON;
Analog Comparator mode 4: reference value GAx, output ON;
Analog Comparator mode 5: reference value GAx, output ON;
Analog Comparator mode 6: reference value GAx, output ON;
Analog Comparator mode 7: reference value GAx, output ON;
Example for program and edit:
Analog Comparison Mode 1
FBD display Parameter display
Enable Input
Analog Input
Analog Input
Parameter
Reference
B003 (G01) output ON when the value of A01 in between (A05-2.50) ~ (A05+2.50);
Parameter display current value of Ax and Ay when running mode;
Analog Comparison Mode 2
FBD display Parameter display
Enable Input
Analog Input
Analog Input
Parameter
Reference
B003 (G01) output ON when the value of A01 is not greater than the value of A05;
Parameter display current value of Ax and Ay when running mode;