Chapter 3 Program Tools 48
Analog input A01~A04: 0~9.99V
Expansion Analog input A05~A08: 0~9.99V or 0~20.00mA
Expansion temperature analog input AT01~AT04: -100.0~600.0 Cent degree or -148.0~1112.0 Fahrenheit degree
Expansion analog output AQ01~AQ04: 0~10.00V or 0~20.00mA
Setting voltage mode or current mode, more information to see: Chapter 4: Relay Ladder Logic
Programming-AQ(Analog Output).
Hidden I/O interface function:
SG2 can display the states for 14 sorts of coil, as shown in below table. Each bit of DRD8 current value (except
bit 14 and 15) determines the corresponding IO interface to be displayed or not. When one bit equal 1, the
corresponding I/O interface is hidden (mean you can’t display the I/O interface by pressing SEL+ or ).
Num I/O interface DRD8 current value
0 I/Z/Q: I01~I0C,Z01~Z04,Q01~Q08
Bit0:* always display
1 X/Y X01~X0C,Y01~Y0C Bit1:=0 Display; =1 Not displayed
2 M1 M01~M1F Bit2:=0 Display; =1 Not displayed
3 M2 M20~M3F Bit3:=0 Display; =1 Not displayed
4 N1 N01~N1F Bit4:=0 Display; =1 Not displayed
5 N2 N20~N3F Bit5:=0 Display; =1 Not displayed
6 T T01~T1F Bit6:=0 Display; =1 Not displayed
7 C C01~C1F Bit7:=0 Display; =1 Not displayed
8 R R01~R1F Bit8:=0 Display; =1 Not displayed
9 G G01~G1F Bit9:=0 Display; =1 Not displayed
10 A1 A01~A04 Bit10:=0 Display; =1 Not displayed
11 A5 A05~A08 Bit11:=0 Display; =1 Not displayed
12 AT AT01~AT04 Bit12:=0 Display; =1 Not displayed
13 AQ AQ01~AQ04 Bit13:=0 Display; =1 Not displayed