VOT1; Rev 1.5; EN; 5.11.2015
TKT66 – Installation and maintenance
Use this option to change the status of the
automatic configuration.
The default setting is 0, meaning that the
automatic configuration is OFF.
NOTE: This function only works in addressable
monitoring. If circuit monitoring is chosen, the
central battery unit needs to be reconfigured
after changing the circuit load.
To change the automatic configuration
status,
1. Go to the menu with the
MENU / OK button.
2. Press the BROWSE button until
the AUTO CONF. led is lit.
3. Press the SET button until the
value you wish to select shows in
the display.
For example 1 = Automatic
configuration is on.
The automatic configuration settings
are changed.
Use this setting to choose between automatic
and manual tests.
7-segments-
display
The first section in the 7-segment-display
determines every how often the luminaire
test is made, from 1 to 7, meaning the
number of days. If the number is 1, the test
is made every day, or if it is 7, the test is
done once a week.
The number of the second segment
determines the settings of the luminaire
tests.
0 = Luminaire and battery test, both manually.
1 = Luminaire and battery test, both
automatically (presumption).
2 = Luminaire test automatically, battery test
manually.
3 = Luminaire test manually, battery test
automatically.
The automatic luminaire test is made once per
day on the chosen time of the day.
The automatic battery test is made twice a year
(4
th
of January and 4
th
of July).
To choose between automatic and
manual tests,
1. Go to the menu with the
MENU / OK button.
2. Press the BROWSE button until
the TEST SELECT led is lit.
3. Press the SET button until the
value you wish to select shows in
the display.
The testing settings have been
changed.