VOT1; Rev 1.5; EN; 5.11.2015
TKT66 – Installation and maintenance
64
APPENDIX 8: Menu selections
LED Description 0
1 2 3 4 5 6 7 10
1 Report
print report
2
Testing
Lumi. Test
start
Lumi. Test
cancel
Batt. Test
start , 2/3
duration time
Batt.
Test
start ,
full
duration
time
Batt.
Test
start , to
deep
discharge
limit
Batt.
Test
cancel /
batt.
error
confirm
reconfigu
ration
3 Setup
Settings locked
Settings
possible
4 Auto conf.
not in use in use
5 Test select
first digit, luminaire
test interval
test every day
test every
second day
test every
third day
test ever
fourthy
day
test
every
fifth day
test
every
sixth day
test
every
seventh
day
second digit
luminaire and
battery test
manually
luminaire
and battery
test
automatically
luminaire test
automatically,
battery test
manually
luminaire
test
manually,
battery test
automatically
6 Sensitivity
7 Luminaire test time
8 Delay time
9 Cent. Number
10 Battery level
11 Duration
12 Years
13 Months
14 Days
15 Huors
16 Minutes
To set year. Last two digits of year (e.g. 12 = 2012)
To set month.
To set day.
To set hour. 24h system.
To set minutes.
Selection
Sensitivity value selection in circuit monitoring. See instructions in chapter 5.3.
Luminaire test time selection. Press SET button until correct time is selected. E.g. 15=15.00=3pm.
Delay time when switching from battery operation to mains voltage. Value in minutes.
Central Battery Unit individual number. Useful in reports and central monitoring systems.
Voltage level that battery test stops. Default is 210V(recommendation). Value is 200V + selection. E.g. your selection
is 20 -> battery test stop level is 200V + 20 V = 220V.
Selection of duration time, 1h or 3h battery operation time.