EasyManua.ls Logo

TemperZone Econex Pro - 7. OPERATION; BMS Operation via BACnet; Standalone Unit Operation Mode; Indoor Fan Configuration

TemperZone Econex Pro
16 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
- 7 -
11. Scroll down () to the next page.
12. Scroll down () to the next page.
Quick access to a daily schedule to set the
Unoccupied hours.
Return to the Main Menu (↵)
Indoor Fan Conguration
13. Main Menu/Settings/Indoor Fan Cong./Fan Control
Method (1).
For setting of the fan control method.
Options: constant air ow or speed controlled,
0-10V dc input
14. Main Menu/Settings/Fan Cong./Constant Air Flow
(2).
Scroll down to the next page. A pressure sensor is
factory tted to the indoor fans allowing the air ow
to be automatically controlled. Set the ow in l/s.
15. Menu/Settings/Fan Cong./No Load Fan (3).
For setting of the fan staus when there is no load on
the system.
Return to the Main Menu (↵)
Damper Conguration
16. Main Menu/Settings/Damper Cong.
Select ‘Damper Cong.’ (↵)
For units supplied with Economiser Package,
Economy Mode is enabled.
Scroll down () to the next page
17. For units supplied with Economiser Package,
Enthalpy Control is the recommended control
method.
Options are available to control the economiser
dampers: unoccupied mode, damper stroke, damper
direction, fresh air inlet
Scroll down () to see the next pages.

Related product manuals