©Copyright Task Force Tips LLC 2002-2021 8 LIN-030 May 21, 2021 Rev18
4.4 REACH AND TRAJECTORY
All reach data was taken in still air conditions at an elevation of 30 degrees.
Figure 4.4A
Figure 4.4B
CAUTION
Dents or nicks in the nozzle tip can seriously affect the stream reach or pattern, which may increase
the risk of injury due to exposure. Care must be taken to avoid dents or nicks in the nozzle tip.
Ultimatic 100 psi (7 bar) Version
Curve
A B C D E F A B C D E F
Flow (gpm)
10 25 50 75 100 125 (L/min) 38 95 189 284 379 473
Pressure (psi)
28 69 84 91 110 122 (bar) 1.9 4.8 5.8 6.3 7.6 8.4
Reaction (lbs)
3 10 23 36 53 70 (kgf) 1 5 10 16 24 32
Ultimatic 75 psi (5 bar) Version
Curve
A B C D E A B C D E
Flow (gpm)
10 25 50 75 100 (L/min) 38 95 189 284 379
Pressure (psi)
26 46 59 69 80 (bar) 1.8 3.2 4.1 4.8 5.5
Reaction (lbs)
3 9 19 31 45 (kgf) 1 4 9 14 20
100 psi/ 7 bar Version
MODEL
BGH-125
SHOWN
ULTIMATIC 100 PSI (7 BAR) VERSION
Automatic Pressure Control Flow Range:
10-125 gpm @ 100 psi
40-500 L/min @ 7 bar
ULTIMATIC 75 PSI (5 BAR) VERSION
Automatic Pressure Control Flow Range:
10-100 gpm @ 75 psi
40-400 L/min @ 5 bar