Manual 0-2844 A-1 APPENDIX
APPENDIX 1: INPUT WIRING REQUIREMENTS
NOTES
Refer to Local and National Codes or local authority having jurisdiction for proper wiring requirements.
Cable size is de-rated based on the Duty Cycle of the equipment.
The suggested sizes are based on flexible power cable with power plug installations. For hard-wired installations refer
to local or national codes.
Cable conductor temperature used is 167° F (75° C).
An energy limiting fuse UL Class RK-1 (examples: BUSS LPS/LPN-RK or Gould-Shawmut AZK-A6K) should be
used to minimize damage to Plasma Cutting, Welding or power distribution equipment.
NEVER use replaceable element fuses like UL Class H, or "one-time" fuses like UL Class K5.
Power Input Current Input
Voltage Frequency 3-Ph 3-Ph Fuse (Amps)
Wire (mm
2
)
(Volts) (Hz) (kVA) (Amps) 3-Ph 3-Ph
CE CutMaster 50 400 50/60 7.9 11.5 15 4
CE CutMaster 75 400 50 11.1 16 20 4
CE CutMaster 100 400 50 13.9 20 25 4
Input Suggested Sizes (See Notes)
Line Voltages with Suggested Circuit Protection and Wire Sizes
Based on National Electric Code and Canadian Electric Code