EasyManua.ls Logo

Thytronic NC20 - Page 200

Thytronic NC20
227 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
200
200
NC2 0 - Manual - 01 - 2015
APPENDIX
200
200
NC2 0 - Manual - 01 - 2015
APPENDIX
Description Parameter Unit Setting range
Disabling Dth> by 50-51 start Dth>disby50-51
OFF | ON
Dth> Trip relays Dth>-K
K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
Dth> Trip LEDs Dth>-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8 |
L9 | L10
Phase overcurrent - 50/51 RMS
I>AL Element
Setpoints
I>AL Enable I>AL Enable
OFF | ON
ICLP>AL Mode ICLP>AL Mode
OFF | ON - Element blocking | ON - Change setting
ICLP>AL Activation time
Value
s
0.00 ... 9.99 step = 0.01
10.0 ... 100.0 step = 0.1
I>AL Logical block I>ALBLK1
OFF | ON
I>AL Start relays I>ALST-K
K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
I>AL Trip relays I>ALTR-K
K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
I>AL Start LEDs I>ALST-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8 |
L9 | L10
I>AL Trip LEDs I>ALTR-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8 |
L9 | L10
Defi nite time
50/51 Alarm threshold defi nite time
State
OFF | ON
Pickup value
In
0.100 ... 0.999 step = 0.001
1.00 ... 10.00 step = 0.01
I>ALdef within CLP ICLP>ALdef In
0.100 ... 0.999 step = 0.001
1.00 ... 10.00 step = 0.01
I>ALdef Operating time
Value
s
0.03 ... 9.99 step = 0.01
10.0 ... 99.9 step = 0.1
100 ... 200 step = 1
I> Element
Setpoints
I> Enable I> Enable
OFF | ON
I> Curve type I>Curve
IEC/BS A | IEC/BS B | IEC/BS C | ANSI/IEEE MI
| ANSI/IEEE VI | ANSI/IEEE EI | CAPACITOR |
DEFINITE
ICLP> Mode ICLP> Mode
OFF | ON - Element blocking | ON - Change setting
ICLP> Activation time
Value
s
0.00 ... 9.99 step = 0.01
10.0 ... 100.0 step = 0.1
I> Reset time delay
Value
s
0.00 ... 9.99 step = 0.01
10.0 ... 100.0 step = 0.1
I> Logical block I>BLK1
OFF | ON
I> Input selective block I>BLK2IN
OFF | ON
I> Output selective block I>BLK2OUT
OFF | ON
I> Breaker failure I>BF
OFF | ON
I>AL Disabling by I> I>ALdisbyI>
OFF | ON
I> Start relays I>ST-K
K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
I> Trip relays I>TR-K
K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
I> Start LEDs I>ST-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8 |
L9 | L10
I> Trip LEDs I>TR-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8 |
L9 | L10
Defi nite time
50/51 First threshold defi nite time
State
OFF | ON

Table of Contents